Comparison of Performances Between R404A and AZ50 Used in Commercial Refrigeration
نویسندگان
چکیده
Denis CLODIC Centre d'Energetique ·Ecole des Mines de Paris 60, boulevard Saint-Michel· F • 75272 PARIS Cedex 06 A test bench has been developed consisting in an open display-case and a refrigerating system composed mainly of four hermetic compressors, an air cross-current condenser and an evaporator. The evaporating temperature of -40°C allows to keep the temperature of the products at ·18°C for a room temperature of 25°C and a relative humidity of 50%. The test bench is designed in order to acquire the following data: ·temperature in the core of products · temperature of blowing air · temperature of returned air · temperature and humidity of air in the room ·different temperatures at the surface of the evaporator · high and low pressure of refrigerating system · 1 0 different temperatures at the surface of the condenser · temperature of air at the two ends of the condenser ·flow of the cooling air at the condenser · electric power consumed by the compressors -temperatures of the compressors (suction, discharge, oil) composition of the vapor at the suction and the discharge of compressors · composition of the liquid in the receiver. A testing method was defined to allow comparison performances between R404A and AZ50 with respect to refrigerating capacity, energy efficiency as well as preservation of inner temperature of products laying into the display case.
منابع مشابه
Analysis of the Operating Characteristics of a Low Evaporation Temperature R404A Refrigeration System
A refrigeration system which was originally designed using R502 as refrigerant was rebuilt to adapt the special requirements of R404A. The experiments, both for R502 and R404A, on this system were done and some parameters such as evaporating temperature, condensing temperature, discharge temperature, compressor input power and so on were measured under different working conditions. Then the ope...
متن کاملNumerical Simulation of R410a-R23 and R404A-R508B Cascade Refrigeration System
Capacity and efficiency of any refrigerating system diminish rapidly as the difference between the evaporating and condensing temperature is increased by a reduction in the evaporator temperature. The single stage vapour compression refrigeration system using various refrigerants are limited to an evaporator temperature of -40 0C. Below temperature of -40 0C the either cascade refrigeration sys...
متن کاملNumerical Simulation of Heat Exchanger Area of R410A-R23 and R404A-R508B Cascade Refrigeration System at Various Evaporating and Condensing Temperature
Capacity and efficiency of any refrigerating system diminish rapidly as the difference between the evaporating and condensing temperature is increased by reduction in the evaporator temperature. The single stage vapour compression refrigeration system is limited to an evaporator temperature of -40 C. Below temperature of -40 C the either cascade refrigeration system or multi stage vapour compre...
متن کاملPerformance Evaluation and Optimal Design of Supermarket Refrigeration Systems with Supermarket Model “SuperSim”, Part II: Model Applications
As described in Part I, the supermarket simulation software “SuperSim” with its integrated refrigeration, building and HVAC system models, can be used to evaluate, compare and optimize alternative supermarket refrigeration systems. In Part II the model was used to evaluate and compare the performance of a CO2 booster refrigeration system with that of a conventional R404A multiplex system in a s...
متن کاملExergy, exergoeconomic and exergoenvironmental studies and optimization of a novel triple-evaporator refrigeration cycle with dual-nozzle ejector using low GWP refrigerants
In this work, a novel dual-nozzle ejector enhanced triple-evaporator refrigeration cycle (DETRC) without separator is proposed to improve the performance of the conventional ejector one (CETRC). The performance of DETRC is analyzed and compared with CETRC in term of energy coefficient of performance (COPen). Under given operating conditions, the COPen improvement of the no...
متن کامل