Evaluation of Legionella Air Contamination in Healthcare Facilities by Different Sampling Methods: An Italian Multicenter Study

نویسندگان

  • Maria Teresa Montagna
  • Osvalda De Giglio
  • Maria Luisa Cristina
  • Christian Napoli
  • Claudia Pacifico
  • Antonella Agodi
  • Tatjana Baldovin
  • Beatrice Casini
  • Maria Anna Coniglio
  • Marcello Mario D’Errico
  • Santi Antonino Delia
  • Maria Grazia Deriu
  • Marco Guida
  • Pasqualina Laganà
  • Giorgio Liguori
  • Matteo Moro
  • Ida Mura
  • Francesca Pennino
  • Gaetano Privitera
  • Vincenzo Romano Spica
  • Silvia Sembeni
  • Anna Maria Spagnolo
  • Stefano Tardivo
  • Ida Torre
  • Federica Valeriani
  • Roberto Albertini
  • Cesira Pasquarella
چکیده

Healthcare facilities (HF) represent an at-risk environment for legionellosis transmission occurring after inhalation of contaminated aerosols. In general, the control of water is preferred to that of air because, to date, there are no standardized sampling protocols. Legionella air contamination was investigated in the bathrooms of 11 HF by active sampling (Surface Air System and Coriolis®μ) and passive sampling using settling plates. During the 8-hour sampling, hot tap water was sampled three times. All air samples were evaluated using culture-based methods, whereas liquid samples collected using the Coriolis®μ were also analyzed by real-time PCR. Legionella presence in the air and water was then compared by sequence-based typing (SBT) methods. Air contamination was found in four HF (36.4%) by at least one of the culturable methods. The culturable investigation by Coriolis®μ did not yield Legionella in any enrolled HF. However, molecular investigation using Coriolis®μ resulted in eight HF testing positive for Legionella in the air. Comparison of Legionella air and water contamination indicated that Legionella water concentration could be predictive of its presence in the air. Furthermore, a molecular study of 12 L. pneumophila strains confirmed a match between the Legionella strains from air and water samples by SBT for three out of four HF that tested positive for Legionella by at least one of the culturable methods. Overall, our study shows that Legionella air detection cannot replace water sampling because the absence of microorganisms from the air does not necessarily represent their absence from water; nevertheless, air sampling may provide useful information for risk assessment. The liquid impingement technique appears to have the greatest capacity for collecting airborne Legionella if combined with molecular investigations.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Response to Comments on Montagna et al. “Evaluation of Legionella Air Contamination in Healthcare Facilities by Different Sampling Methods: An Italian Multicenter Study” Int. J. Environ. Res. Public Health 2017, 14, 670

We would like to thank Collins andWalker for their comments and for acknowledging that this is an area requiring more research to improve our basic understanding of Legionella [1]. [...].

متن کامل

Comment on Montagna, et al. Evaluation of Legionella air contamination in healthcare facilities by different sampling methods: An Italian multicenter study. Int. J. Environ. Res. Public Health 2017, 14, 670

In their recent article, Montagna et al. describe a multicenter study investigating the presence of Legionella in water and air samples of Italian healthcare facilities [1]. This is an interesting study that highlights some important gaps in our basic understanding of Legionella. One of the limitations of the study regarded the lack of information on the tap outlets (e.g., design of tap, flow r...

متن کامل

Italian multicenter study on infection hazards during dental practice: Control of environmental microbial contamination in public dental surgeries

BACKGROUND The present study assessed microbial contamination in Italian dental surgeries. METHODS An evaluation of water, air and surface microbial contamination in 102 dental units was carried out in eight Italian cities. RESULTS The findings showed water microbial contamination in all the dental surgeries; the proportion of water samples with microbial levels above those recommended decr...

متن کامل

Contamination of the cold water distribution system of health care facilities by Legionella pneumophila: do we know the true dimension?

German water guidelines do not recommend routine assessment of cold water for Legionella in healthcare facilities, except if the water temperature at distal sites exceeds 25°C. This study evaluates Legionella contamination in cold and warm water supplies of healthcare facilities in Hesse, Germany, and analyses the relationship between cold water temperature and Legionella contamination. Samples...

متن کامل

Environmental microbial contamination in dental setting: a local experience.

INTRODUCTION Patients and operators are exposed during dental practice to an infective risk, which derives especially from microorganisms suspended in aerosols. Environmental microbiological monitoring in dental settings represents a good instrument to detect critical situations. METHODS In order to investigate environmental microbial contamination level in a local reality, we analyzed water,...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره 14  شماره 

صفحات  -

تاریخ انتشار 2017