Flow Electrification Measurements of Transformer Insulation using a Couette Flow Facility - Dielectrics and Electrical Insulation, IEEE Transactions on
نویسنده
چکیده
A rotating cylindrical electrode apparatus, which provided cylindrical Couette flow, was used to simulate flow electrification in an electric power transformer. The apparatus had Shell Diala A transformer oil filling the annulus between coaxial cylindrical stainless steel electrodes that were either bare metal, or covered by a thin copper sheet and/or EHV-Weidmann HiVal pressboard insulation. Extensive experiments characterized the time transient and steady state behavior of the electrification through measurements of the volume charge density, the terminal voltage, and the terminal current as the system was driven out of equilibrium by changes in the flow rate (inner cylinder rotation rates of 100 to 1400 rpm, Reynolds numbers of 5 x l o3 to 5 x lo5), temperature (15 to 70'0, insulation moisture content (0.5 to 20 ppm in the oil), applied voltage (0 to 2 kV dc), and concentration of the non-ionizable antistatic additive 1,2,3 benzotriazole (BTA, 0 to 60 ppm). Generally, the electrification increased with flow rate and temperature but the BTA appeared to cause competing effects: it decreased the volume charge density on the liquid side of the interface by a factor of 4, which reduces the electrification, but also decreased the oil conductivity by a factor of 10, which enhances the electrification. A critical oil BTA concentration of 5 to 8 ppm minimized the electrification. The volume charge density was sensitive to the current flowing through the interface and surface charge accumulation. With pressboard covering the cylinders, the electrification effects of the temperature and moisture were decoupled during the transient following step reductions in the temperature. The oil moisture content did not affect the oil conductivity significantly, but the volume charge density varied inversely with the moisture content during an initial equilibration period just after the oil had been added to the system. The highest electrification was observed during this equilibration period.
منابع مشابه
Optical, Electrical and Electromechanical Measurement Methodologies of Field, Charge and Polarizatio - Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE
A selective review is presented of the use of optical, electrical, and electromechanical measurement methodologies of the electric field, charge, conductivity, and permittivity in dielectrics. Kerr electro-optic measurements are presented to demonstrate how volume charge distributions can distort the electric field distribution :significantly and how the field and charge distributions depend on...
متن کاملA Chemical Reaction-based Boundary Condition For Flow Electrification - Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE
A physical model is developed for the charge transfer boundary condition in semi-insulating liquids. The boundary condition is based upon interfacial chemical reactions and extends established relations for the interface by including the effects of interfacial surface charge and charge desorption at the interface. A steady state model for flow electrification in a rotating cylindrical electrode...
متن کاملMoisture solubility for differently conditioned transformer oils - Dielectrics and Electrical Insulation, IEEE Transactions on [see also Electrical Insulation, IEEE
It is important to monitor the moisture content of transformer oil in a transformer. One parameter of particular interest is the moisture solubility of transformer oil. It has been reported that transformer oils under different conditions have different solubility. Measurements of solubility for four different types of conditioned oil are presented in this paper: fresh Shell Diala AX oil, lab-a...
متن کاملA Feasible Solution to Distinguish the Transformer Winding Deformation from Insulation Characteristic Impacts on FRA Spectrum
Frequency Response Analysis (FRA) is popular technique which has been used since the last decade as a diagnostic method for transformers. However, accurate interpretation of FRA measurements is still challenging. Recent studies reveal that apart from winding deformation, FRA data can also be influenced by moisture variation in transformer paper insulation. Hence, a specific transformer’s model ...
متن کاملEstimation of Moisture in Transformer Insulation Using Dielectric Frequency Response Analysis by Heuristic Algorithms
Transformers are one of the most valuable assets of power systems. Maintenance and condition assessment of transformers has become one of the concerns of researchers due to huge number of transformers has been approached to the end of their lifetimes. Transformer’s lifetime depends on the life of its insulation and the insulation’s life is strongly influenced by its moisture attraction as well....
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -
تاریخ انتشار 2009