Model for Predicting DC Flashover Voltage of Pre-Contaminated and Ice-Covered Long Insulator Strings
نویسندگان
چکیده
In the current study, a multi-arc predicting model for DC critical flashover voltage of iced and pre-contaminated long insulator strings under low atmospheric pressure is developed. The model is composed of a series of different polarity surface arcs, icicle-icicle air gap arcs, and residual layer resistance. The calculation method of the residual resistance of the ice layer under DC multi-arc condition is established. To validate the model, 7-unit and 15-unit insulator strings were tested in a multi-function artificial climate chamber under the coexistent conditions of low air pressure, pollution, and icing. The test results showed that the values calculated by the model satisfactorily agreed with those experimentally measured, with the errors within the range of 10%, validating the rationality of the model.
منابع مشابه
DC Flashover Performance of Ice-Covered Composite Insulators with Parallel Air Gaps
DC flashover performance of ice-covered composite insulators with a parallel air gap (CI/PAG) is an important technical consideration when such insulators are used to isolate ground wires for the purpose of DC ice-melting. Tests on tension and suspension types of CI/PAG were thus carried out in the artificial climate chamber to investigate their DC icing flashover performance. The influences of...
متن کاملIon Migration in the Process of Water Freezing under Alternating Electric Field and Its Impact on Insulator Flashover
Ice flashover threatens the security and reliability of power transmission. However, the ice flashover mechanism of insulators remains poorly understood. This study analyses water droplet freezing and ion distribution in ice layer under alternating electric field. It also investigates ion migration during icing process of insulator string under alternating electric field and its effects on insu...
متن کاملEffects of Disc Insulator Type and Corona Ring on Electric Field and Voltage Distribution over 230-kV Insulator String by Numerical Method
Insulator strings with several material and profiles are very common in overhead transmission lines. However, the electric field and voltage distribution of insulator string is uneven which may easily lead to corona, insulators’ surface deterioration and even flashover. So the calculation of the electric field and voltage distribution along them is a very important factor in the operation time....
متن کاملDesignation of an Indicator for flashover prediction of porcelain and glass insulators based on experimental tests.
Flashover of polluted insulators in contaminated areas is one of the most important factors influencing the operation of transmission and distribution lines and finally line outages. Therefore, it is essential to prevent and detect flashover in the insulators. Hence, utilizing the insulator status monitoring systems and predicting their functions have absorbed a lot of attention over the recent...
متن کاملImpact of Pollution Location on Time and Frequency Characteristics of Leakage Current of Porcelain Insulator String under Different Humidity and Contamination Severity
One of the important factors influencing outdoor insulators performance is pollution phenomenon. The pollution, especially during humidity condition, reduces superficial resistance of insulator and lead to a flow of Leakage Currents (LC) on the insulator surface, which may result in total flashover. The LC characteristics are affected by parameters such as nature and severity of pollution. Loca...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
دوره شماره
صفحات -
تاریخ انتشار 2011