HC-290 (Propane) Vaporisation Inside a Brazed Plate Heat Exchanger

نویسندگان

  • Giovanni A. Longo
  • Giovanni A. LONGO
چکیده

This paper presents the heat transfer coefficients measured during HC-290 (Propane) vaporisation inside a brazed plate heat exchanger: the effects of heat flux, saturation temperature (pressure) and outlet conditions are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature (pressure) and great sensitivity to heat flux and outlet conditions. The saturated boiling experimental heat transfer coefficients are compared with two well-known equations for nucleate boiling (Cooper (1984) and Gorenflo (1993)). The mean absolute percentage deviation between experimental and calculated heat transfer coefficients is 26.9% and 16.6% for Cooper (1984) and Gorenflo (1993) equation respectively. The heat transfer measurement has been complemented with IR thermography in order to quantify the portion of the heat transfer surface affected by vapour super-heating.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Heat Transfer and Pressure Drop During HC-600a (Isobutane) Condensation Inside a Brazed Plate Heat Exchanger

This paper presents the heat transfer coefficients and the pressure drop measured during HC-600a (Isobutane) condensation inside a brazed plate heat exchanger: the effects of saturation temperature, refrigerant mass flux and vapour super-heating are investigated. The heat transfer coefficients show weak sensitivity to saturation temperature and great sensitivity to refrigerant mass flux. At low...

متن کامل

Experimental Analysis of Heat Transfer and Friction Factor in Plate Heat Exchanger with Different Orientations Using Al2O3 Nanofluids

Experimental investigations has been done to find out the heat transfer characteristics and friction factor of water based Al2O3 nanofluids as a coolant in  brazed plate heat exchanger. Plate heat exchanger either use horizontally or vertically. The base plate of the plate heat exchanger was kept inclined at (0⁰, 30⁰ ,60⁰, 90⁰). The experimentation have been done on the two different concentrat...

متن کامل

Evaporation and Condensation Heat Transfer Performance of Flammable Refrigerants in a Brazed Plate Heat Exchanger

Average Nusselt numbers were measured for R22, R290, R290/600a, and R32/152a undergoing evaporation and condensation in a brazed plate heat exchanger. The refrigerants experienced wavy, stratified flow at low heat and mass fluxes, 1.3 kW/m2 to 8.3 kW/m2 and 1.6 kg/m2 s to 19 kg/m 2 s, respectively. Heat transfer correlations from the literature for in-tube and channel flow of refrigerants with ...

متن کامل

The Influence of Brazing on Very Compact Heat Exchanger Surfaces

Three geometrically similar offset rectangular platefin surfaces with area densities in the range from goo to 2000 ft 2/ft3 were tested to establish the heat transfer., j-NR~ and flow friction, f-NR, characteristics. The Reynolds number range was from 60 to 3000. One surface was unbrazed while the other two, because of a two-to-one difference in plate, fin and offset spacing dimensions~ were ch...

متن کامل

Heat transfer enhancement in a spiral plate heat exchanger model using continuous rods

This study presents an innovative and simple way to increase the rate of heat transfer in a spiral plate heat exchanger model. Several circular cross-section rods, as continuous vortex generators, have been inserted within the spiral plate heat exchanger in the cross-stream plane. The vortex generators are located at various azimuth angles of α=30◦, 60◦, 90◦, and 120◦ with non-dimensional diame...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2014