Optimal Analysis of Grounding System Design for Distribution Substation

نویسندگان

  • T. Lantharthong
  • N. Rugthaicharoencheep
  • A. Phayomhom
چکیده

Abstract—This paper presents the electrical effect of two neighboring distribution substation during the construction phase. The size of auxiliary grounding grid have an effect on entire grounding system. The bigger the size of auxiliary grounding grid, the lower the GPR and maximum touch voltage, with the exception that when the two grids are unconnected, i.e. the bigger the size of auxiliary grounding grid, the higher the maximum step voltage. The results in this paper could be served as design guideline of grounding system, and perhaps remedy of some troublesome grounding grids in power distribution’s system. Modeling and simulation is carried out on the Current Distribution Electromagnetic interference Grounding and Soil structure (CDEGS) program. The simulation results exhibit the design and analysis of power system grounding and perhaps could be set as a standard in grounding system design and modification in distribution substations.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Back-flashover Investigation of HV Transmission Lines Using Transient Modeling of the Grounding Systems

The article presents the transients analysis of the substation grounding systems and transmission line tower footing resistances which can affect to the back-flashover (BF) or overvoltage across insulator chain in an HV power systems by using EMTP-RV software. The related transient modeling of the grounding systems is based on a transmission line (TL) model with considering the soil ionization....

متن کامل

طراحی بهینه، ایمن و اقتصادی سیستم زمین پست‌های فشارقوی

Due to both safety and economic issues, exhaustive and optimal design of the grounding system of high voltage substations is one of the most important, expensive, sensitive, and complicated problems of the high voltage substations. In this paper, a novel designing method is proposed which consist of seven fundamental steps. The method is based on the ANSI/IEEE Std. 80-2000 standard. Most of the...

متن کامل

A MULTISTAGE EXPANSION PLANNING METHOD FOR OPTIMAL SUBSTATION PLACEMENT

Optimal distribution substation placement is one of the major components of optimal distribution system planning projects. In this paper optimal substation placement problem is solved using Imperialist Competitive Algorithm (ICA) as a new developed heuristic optimization algorithm. This procedure gives the optimal size, site and installation time of medium voltage substation, using their relate...

متن کامل

Optimal Design of Grounding System for HV/ EHV Substations in Two Layered Soil

Successful operation of entire power system depends to a considerable extent on efficient and satisfactory performance of substations. Hence substations in general can be considered as heart of overall power system. In any substation, a well designed grounding plays an important role. Since absence of safe and effective grounding system can result in mal-operation or non-operation of control an...

متن کامل

Analysis of a Large Grounding System and Subsequent Field Test Validation Using the Fall of Potential Method

This paper examines various aspects of the design process and subsequent field test measurements of a large and complex substation grounding system. The study and measurements show that soil layering and lead interference can have a significant impact on the appropriate test location that yields the exact substation ground impedance. Applying a specific percentage rule such as the 61.8% rule fo...

متن کامل

ذخیره در منابع من