Particle Swarm Optimization Based Interconnected Hydro-Thermal AGC System Considering GRC and TCPS
نویسندگان
چکیده
Abstract—This paper represents performance of particle swarm optimisation (PSO) algorithm based integral (I) controller and proportional-integral controller (PI) for interconnected hydro-thermal automatic generation control (AGC) with generation rate constraint (GRC) and Thyristor controlled phase shifter (TCPS) in series with tie line. The control strategy of TCPS provides active control of system frequency. Conventional objective function integral square error (ISE) and another objective function considering square of derivative of change in frequencies of both areas and change in tie line power are considered. The aim of designing the objective function is to suppress oscillation in frequency deviations and change in tie line power oscillation. The controller parameters are searched by PSO algorithm by minimising the objective functions. The dynamic performance of the controllers I and PI, for both the objective functions, are compared with conventionally optimized I controller.
منابع مشابه
Differential evolution algorithm based automatic generation control for interconnected power systems with non-linearity
Automatic Generation Control (AGC); Boiler dynamics; Generation Rate Constraint (GRC); Governor dead band; Proportional Integral Derivative (PID) controller; Differential Evolution (DE) algorithm Abstract This paper presents the design and performance analysis of Differential Evolution (DE) algorithm based Proportional–Integral (PI) and Proportional–Integral–Derivative (PID) controllers for Aut...
متن کاملEffect of Cuckoo Search Optimized Integral - Double Derivative Controller with Tcps for Containing Oscillations in Automatic Generation Control (agc)
In this paper, integral plus double derivative (IDD) in coordination with Thyristor Controlled Phase Shifter (TCPS) is applied for the first time in automatic generation control (AGC) system. Comparative studies on the performance of different classical controllers viz. integral (I), proportional plus integral (PI), proportional plus integral plus derivative (PID) and integral plus double deriv...
متن کاملOptimizing the AGC system of a three-unequal-area hydrothermal system based on evolutionary algorithms
This paper focuses on expanding and evaluating an automatic generation control (AGC) system of a hydrothermal system by modelling the appropriate generation rate constraints to operate practically in an economic manner. The hydro area is considered with an electric governor and the thermal area is modelled with a reheat turbine. Furthermore, the integral controllers and electri...
متن کاملPSO based Single and Two Interconnected Area Predictive Automatic Generation Control
This paper presents a Particle Swarm Optimization (PSO) based Model Predictive Control (MPC) scheme applied to Automatic Generation Control (AGC) systems. The proposed scheme formulates the MPC as an optimization problem and PSO is used to find its solution. Single area AGC model is taken incorporating Generation Rate Constraint (GRC) nonlinearities and constraints on the control input. Two int...
متن کاملPSO Application to Optimization of AGC in Interconnected Power System with Diverse Sources of Power Generation
In this paper, automatic generation control (AGC) of two area interconnected power system having diverse sources of power generation is studied. A two area power system comprises power generations from hydro, thermal and gas sources in area-1 and power generations from hydro and thermal sources in area-2. All the power generation units from different sources are equipped with speed governors. A...
متن کامل