Measured and Modeled Charging of a Stratified Chilled Water Thermal Storage Tank with Slotted Pipe Diffusers

نویسندگان

  • William P. Bahnfleth
  • Jing Song
  • John M. Cimbala
چکیده

As part of ASHRAE Research Project 1185, field data from the constant flow rate charging of a stratified chilled water storage tank with double-ring octagonal slotted-pipe diffusers serving a university chilled water system were compared with results of a transient axisymmetric computational fluid dynamics (CFD) model. Charge processes at flows near design flow rate and 50% of design were modeled. Laminar and turbulent simulations were performed for a range of slot dimensions. Performance of the model was assessed by direct comparison of temperature profiles and by comparison of common thermal performance metrics, including thermocline thickness, lost capacity, and equivalent lost height. The inlet Richardson number based on slot hydraulic radius was found to have the strongest effect on model results. The model Richardson number giving best agreement with the lost height of the field data for near design flow rate was roughly an order of magnitude greater than the Richardson number of the actual diffuser. It is conjectured that this is due to inherent differences between the flow produced by multiple three-dimensional jets in the actual diffuser and the continuous slot of the axisymmetric model. The effect of turbulence varied from negligible to moderate as the Richardson number decreased.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Parametric Study of Charging Inlet Diffuser Performance in Stratified Chilled Water Storage Tanks with Radial Diffusers: Part 1–Model Development and Validation

A computational fluid dynamics (CFD) model has been developed to simulate the flow and heat transfer near a lower radial inlet diffuser in a cylindrical stratified chilled water storage tank during charging. The model was used to perform parametric simulations of inlet diffuser performance in full-scale tanks during thermocline formation, from which first-order correlation relating thermal perf...

متن کامل

Parametric Study of Charging Inlet Diffuser Performance in Stratified Chilled Water Storage Tanks with Radial Diffusers: Part 2–Dimensional Analysis, Parametric Simulations and Simplified Model Development

A parametric study of the thermal performance during charging of a full-scale radial inlet diffuser in a cylindrical stratified chilled water storage tank was performed by applying factorial experimental theory to the results of simulations performed with a validated computational fluid dynamics (CFD) model. Part 1 describes the development and validation of the CFD model. Part 2 summarizes the...

متن کامل

Performance Evaluation of A Stratified Chilled- Water Thermal Storage System

In countries with hot climates, air-conditioning forms a large proportion of annual peak electrical demand, requiring expansion of power plants to meet the peak demand, which goes unused most of the time. Use of well-designed cool storage can offset the peak demand to a large extent. In this study, an air conditioning system with naturally stratified storage tank was designed, constructed and t...

متن کامل

Parametric studies on thermally strati®ed chilled water storage systems

An analysis of the strati®cation decay in thermally strati®ed vertical cylindrical cool storage systems is presented using a one dimensional conjugate heat conduction model. The degree of thermal strati®cation depends upon the length to diameter ratio, wall thickness to length ratio, the thermo-physical properties of the material of the storage tank, the type and thickness of the insulation and...

متن کامل

Optimization of the PCM-integrated solar domestic hot water system under different thermal stratification conditions

Many researchers have investigated how to increase the overall efficiency of solar-driven thermal systems. Several key parameters, such as collector efficiency and storage tank characteristics, may impose some constraints on the annual solar fraction (ASF) of such systems. In this paper, the behaviour of integrating the phase change material (PCM) in SDHW systems is modelled and optimized n...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2003