Rough-Set-based timing characteristic analyses of distance protective relay
نویسندگان
چکیده
Nowadays protection engineers are suffering from very complex implementations of protection system analysis due to massive quantities of inconsistent data, let alone coming from diverse intelligent electronic devices (IEDs). Thus, a novel Rough-Set-based data mining strategy has been formulated to resolve the inconsistency in a distance protective relay’s decision system (i.e. a transformed relay event report) in such a way that the relay’s timing characteristics hidden in its decision algorithm of protection operations have been successfully discovered. Using Rough Set Theory, the inherent uncertainty and vagueness in the relay event report have been resolved using the concepts of discernibility, elementary sets and set approximations. The timing characteristics that have been successfully discovered are in relation to the relay trip assertion activity, impedance element activation, fault characteristics, circuit breaker operation and its overall decision system approximation. © 2012 Elsevier B.V. All rights reserved.
منابع مشابه
Effects of CT and VT Connection Point on Distance Protection of Transmission Lines with FACTS Devices
This paper presents the effects of instrument transformers connection points on the measured impedance by distance relays in the presence of Flexible Alternating Current Transmission System (FACTS) devices with series connected branch. Distance relay tripping characteristic itself depends on the power system structural conditions, pre-fault operational conditions, and especially the ground ...
متن کاملInconsistent Decision System: Rough Set Data Mining Strategy to Extract Decision Algorithm of a Numerical Distance Relay – Tutorial
متن کامل
Providing A New Characteristic for Overcurrent Relays
This with the integration of distributed generation (DG) to meshed distribution systems, the operating time of the protective system becomes a major concern in order to avoid nuisance DG tripping. This paper proposes a new tripping characteristic for directional overcurrent relays (DOCRs) that can achieve a higher possible reduction of overall relays operating time in meshed distribution networ...
متن کاملA new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity
In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...
متن کاملA new interval approach for setting the distance relay zones to achieve perfect selectivity and maximum sensitivity
In this paper, an interval approach is presented to achieve perfect selectivity and maximum sensitivity in distance relay zones, considering uncertainties. For this purpose, first, the uncertainties affecting the settings of the three zones of a distance relay are discussed. Then, by using the Monte-Carlo simulation, the uncertainties are modelled and the impedances seen by the distance relay a...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
- Appl. Soft Comput.
دوره 12 شماره
صفحات -