Reduced Scale Feasibility of Temperature Rise Tests in Substation Connectors
نویسندگان
چکیده
Due to the important increase of the power of electrical transmission and distribution grids expected for the following years, especially in developing countries such as Kenya, Brazil, Philippines or Mexico among others, that have planes of generating energy from clean sources far away from the centres of consumption [1] it becomes a matter of special importance adapting and developing new substation connectors’ testing methods according to the power and temperature regimes at which they are expected to work. The international normative frame of substation connectors established both by the International Electrotechnical Committee (IEC) [2] and the National Electrical Manufacturers Association (NEMA) [3] sets standardized tests for the evaluation of high voltage connectors. These tests are routinely done within the quality plans of the manufacturers. At the moment, testing of substation connectors –and in general switchgear and fittingsis time demanding and costly due to the energy consumed by such tests. The expectations for the following years are that the power consumption of these tests will not do nothing but grow due to expected increase of power of worldwide overhead lines. For instance, today temperature rise tests in substation connectors involve power ranges up to 100 kVA, which are applied in cycles that can last several weeks. These tests are only feasible in few laboratories and at a very high cost: temporary, monetary, energetic and environmental. For this reason, following the line of other technologies such as aeronautics, naval engineering, or automotive as well as other studies done in the field of electrical engineering specially related to the corona effect [4], this study proposes to develop a reduced scale test system to perform temperature rise tests for substation connectors. Both, a theoretical framework based on analytical formulas, finite element method (FEM) simulations and experimental data has been developed to conduct reduced scale temperature rise tests and to set the conditions at which they provide comparable results to those attained in the original scale tests. Firstly, two circular loops (original and reduced scale loops) composed of a power conductor and two terminal connectors were analysed. The aim of this first study was to determine in an easy and trustful way the voltage and current values to be applied in experimental reduced scale tests to achieve the same steady-state temperature as in the original scale temperature rise test. The scale relationship between tests was set in 1:1.8, although the method proposed in this study can deal with any other scale factor. This study was useful in order to have a first sight of the final results of the procedure using substation connectors.
منابع مشابه
Finite Element Analysis to Predict Temperature Rise Tests in High-Capacity Substation Connectors
In the last years there has been a considerable increase in electricity consumption and generation from renewable sources, especially wind and solar photovoltaic. This phenomenon has increased the risk of line saturation with the consequent need of increasing the capacity of some power lines. Considering the high cost and the time involved in installing new power lines, the difficulty in acquir...
متن کاملThree-Dimensional Finite-Element Analysis of the Short-Time and Peak Withstand Current Tests in Substation Connectors
Power devices intended for high-voltage systems must be tested according to international standards, which includes the short-time withstand current test and peak withstand current test. However, these tests require very special facilities which consume huge amounts of electrical power. Therefore, mathematical tools to simulate such tests are highly appealing since they allow reproducing the el...
متن کاملTransient Thermal Modelling of Substation Connectors by Means of Dimensionality Reduction
This paper proposes a simple, fast and accurate simulation approach based on one-dimensional reduction and the application of the finite difference method (FDM) to determine the temperatures rise in substation connectors. The method discretizes the studied three-dimensional geometry in a finite number of one-dimensional elements or regions in which the energy rate balance is calculated. Althoug...
متن کاملRedesign process of a 765 kVRMS AC substation connector by means of 3D-FEM simulations
This paper shows the capabilities of applying the three-dimensional finite element method (3D-FEM) for designing complex-shaped substation connectors to operate at 765 kVRMS AC. To check this methodology, it was analyzed the feasibility of upgrading a 400 kVRMS substation connector to operate at 765 kVRMS. However, both experimental and simulation results conducted according to the ANSI/NEMA CC...
متن کاملFinal Project Summary — PEER Lifelines Program
1. Project goals and objectives This project aimed at developing analytical models and methods for assessing the seismic response of electrical substation equipment connected by assemblies of rigid bus (RB) and flexible strap connectors (FSC) or slider connectors (SC). Also developed is a method to estimate the reliability of electrical substation systems subjected to stochastic earthquake load...
متن کامل