Relay-Based Autotuning of PID Controller for Improved Load Disturbance Rejection
نویسندگان
چکیده
To overcome sluggish load disturbance response for industrial/chemical processes with slow time constant(s), an improved design for on-line autotuning of proportional-integral-derivative (PID) controller is proposed in this paper, based on relay identification of the widely used first-order-plus-deadtime (FOPDT) process model. Using the fitting conditions established for process response at the oscillation frequency under a relay test, the identification algorithm is transparently developed. An analytical controller tuning method is then developed using an asymptotic constraint established thereby for reducing the influence of the slow process time constant on load disturbance rejection. Illustrative examples are given to show the effectiveness and merits of the proposed algorithms.
منابع مشابه
PID controller with improved load-disturbance rejection
In this paper a two-degree-of-freedom (2DOF) IMC structure is considered for integrating process with deadtime to achieve improved load-disturbance response along with the set-point response. Set-point controller is designed considering desired speed of response of the closed-loop system. The load-disturbance controller is designed through direct synthesis approach and both the controllers are ...
متن کاملPerformance Limitation and Autotuning of Inverse Optimal PID Controller for Lagrangian Systems
The PID trajectory tracking controller for Lagrangian systems shows performance limitation imposed by inverse dynamics according to desired trajectory. Since the equilibrium point cannot be defined for the control system involving performance limitation, we define newly the quasiequilibrium region as an alternative for equilibrium point. This analysis result of performance limitation can guide ...
متن کاملLoad Frequency Control Based on Improved Fuzzy Controller in the Microgrid with Thermoelectric Generator
The Microgrid is a small-scale controlled power system, which can be used in islanded mode or in a grid-connected one to provide power. In the islanded Microgrid, the system frequency will be affected severely by the smallest disturbance which can happen due to light inertia in the system. In the independent Microgrid, several generation sources such as solar, wind, and so on can be considered....
متن کاملPID and Predictive PID Control Design for Crushing And Screening
Crushing and screening processes are often regulated using relay-based on/off controls or, when controlled by PID controllers, the control design is limited to a single crusher and its proximity. The design does not necessarily consider process interactions, load disturbances and, in a wider perspective, does not treat a crushing and screening plant as an entity from feeding to product piles. T...
متن کاملIMC based automatic tuning method for PID controllers in a Smith predictor configuration
In this paper, a new approach is presented based on relay autotuning of a plant to find parameters for its control using a Smith predictor. A Smith predictor configuration is represented as its equivalent internal model controller (IMC) which provides the parameters of the proportional-integral (PI) or proportional-integral-derivative (PID) controller to be defined in terms of the desired close...
متن کامل