SVC Light® for powerful flicker reduction from EAF operation

ثبت نشده
چکیده

An ABB SVC Light® rated at 13.2 kV, 0-64 Mvar (capacitive) has been installed at the Gerdau plant in Charlotte, N.C., USA operating an electric arc furnace (EAF) with continuous charging for scrap-based steel production. The EAF, rated at 30/33 MVA, as well as a ladle furnace (LF) rated at 18 MVA are taking their power from a 100 kV supply grid. The fast control of SVC Light will improve the power quality and particularly reduce the flicker levels generated. As a valuable by-product, improved productivity and decreased specific operating costs of the EAF can be attained. SVC Light is extremely well tested, with close to 15 years of track record as a flicker compensator.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

A Comparison between SVC and STATCOM in Flicker Mitigation of Electric Arc Furnace using Practical Recorded Data

Electric arc furnace (EAF) is one of the largest loads in electric power systems. It is highly time varying and nonlinear. Its reactive power variations cause voltage fluctuations in nearby system which is known as flicker. On the other hand the nonlinear voltage-current characteristic causes strong voltage and current harmonics in EAF. To this end Flexible AC Transmission Systems (FACTS) techn...

متن کامل

Voltage Flicker Reduction with Svc in Steel Plant

The voltage flicker is main factor influencing the power quality and SVC is well-proven solution. The flicker reduction requires very short response time, according to the relation analysis between flicker improvement factor and response time. SVC has a fast open-loop control function to achieve effective voltage support. The fast algorithm of flicker reduction is presented here based on synchr...

متن کامل

Chaotic Prediction of Fluctuant Voltage Time Series in EAF Power Supply Grid

In order to solve the problem of voltage flicker produced by electric arc furnace (EAF) operation, it is a prerequisite to analyze the characteristics of voltage time series acquired from AC EAF power supply grid and to conduct voltage prediction based on chaos theory. In this paper, the voltage time series is firstly reconstructed in phase space to determine optimal delay time and embedding di...

متن کامل

Employing Grey System Model for Prediction of Electric Arc Furnace Reactive Power to Improve Compensator Performance

Electric arc furnaces (EAFs) are regarded as one of the major sources of voltage fluctuation in power systems which can contribute to a phenomenon known as flicker. One of the most convenient ways to mitigate flicker is employing static VAr compensators (SVCs). By employing prediction models to forecast EAF reactive power SVC performance can be improved very noticeably. In this paper a Grey sys...

متن کامل

Real-Time Measurement Approach for Tracking the ΔV10 Estimate Value of DC EAF

This investigation develops a revisable method for estimating the estimate value of equivalent 10 Hz voltage flicker (DV10) of a DC Electric Arc Furnace (EAF). This study also discusses three 161kV DC EAFs by field measurement, with those results indicating that the estimated DV10 value is significantly smaller than the survey value. The key point is that the conventional means of estimating DV...