Effect of Load Change on the Thevenin Equivalent Impedance of Power System
نویسندگان
چکیده
This paper discusses the effect of load change on the Thevenin equivalent impedance of power systems. In this paper, the Thevenin equivalent impedance influenced by the derivative of active load with respect to reactive load (dP/dQ) is analyzed. The Thevenin equivalent impedance forms a closed curve in a complex plane and shrinks to one point when voltage collapses. The magnitude of the Thevenin equivalent impedance at the collapse point is equal to the magnitude of the load impedance. Therefore, the impedance match theory still holds under the effect of the load change. These features are verified on a New England 39-bus system.
منابع مشابه
Research on Fault Location in Distributed Network with DG Based on Complex Correlation Thevenin Equivalent and Strong Tracking Filter
With the introduction of distributed generators (DG), the traditional distribution system characterized by radical network becomes a multi-source one. Therefore the accuracy of the equivalent model of distributed generators directly affects the precision of fault location. To solve this problem, this paper proposed a fault location method based on complex correlation Thevenin equivalent and str...
متن کاملModified Impedance-Based OOS Protection Based on On-Line Thévenin Equivalent Estimation
In this paper, a novel approach based on the Thévenin tracing is presented to modified conventional impedance-based out-of-step (OOS) protection. In conventional approach, the OOS detection is done by measuring positive sequence impedance. However, the measured impedance may be change due to different factors such as capacitor bank switching and reactive power compensators that it can cause the...
متن کاملReal Power Generation Scheduling to Improve Steady State Stability Limit in the Java-Bali 500kV Interconnection Power System
This paper will discuss about an active power generator scheduling method in order to increase the limit level of steady state systems. Some power generator optimization methods such as Langrange, PLN (Indonesian electricity company) Operation, and the proposed Z-Thevenin-based method will be studied and compared in respect of their steady state aspects. A method proposed in this paper is built...
متن کاملA New Model for Analysis of Unusual Mal-Operation of Differential Protection Due to the Ultra-Saturation Phenomenon during the Loaded Power Transformer Energization
In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The ultra-saturation phenomenon causes the mal-operation of the power transformer differential protection. So, the description a...
متن کاملA New Model for Analysis of Unusual Mal-Operation of Differential Protection Due to the Ultra-Saturation Phenomenon during the Loaded Power Transformer Energization
In this paper, a new model based on the thevenin equivalent circuit for investigating the ultra-saturation phenomenon during the energization of a loaded power transformer is presented and its effect on the differential protection of the transformer is considered. The ultra-saturation phenomenon causes the mal-operation of the power transformer differential protection. So, the description a...
متن کامل