Detection of Mechanical Deformation in Old Aged Power Transformer Using Cross Correlation Co-Efficient Analysis Method
نویسندگان
چکیده
s – Detection of minor faults in power transformer active part is essential because minor faults may develop and lead to major faults and finally irretrievable damages occur. Sweep Frequency Response Analysis (SFRA) is an effective low-voltage, off-line diagnostic tool used for finding out any possible winding displacement or mechanical deterioration inside the Transformer, due to large electromechanical forces occurring from the fault currents or due to Transformer transportation and relocation. In this method, the frequency response of a transformer is taken both at manufacturing industry and concern site. Then both the response is compared to predict the fault taken place in active part. But in old aged transformers, the primary reference response is unavailable. So Cross Correlation Co-Efficient (CCF) measurement technique can be a vital process for fault detection in these transformers. In this paper, theoretical background of SFRA technique has been elaborated and through several case studies, the effectiveness of CCF parameter for fault detection has been represented.
منابع مشابه
Classification of transformer faults using frequency response analysis based on cross-correlation technique and support vector machine
One of the most important methods for transformers fault diagnosis (especially mechanical defects) is the frequency response analysis (FRA) method. The most important step in the FRA diagnostic process is to differentiate the faults and classify them in different classes. This paper uses the intelligent support vector machine (SVM) method to classify transformer faults. For this purpose, two gr...
متن کاملPower Auto-transformer Mechanical Faults Diagnosis Using Finite Element based FRA
Frequency response analysis (FRA) is a sensitive method established for testing the mechanical integrity of transformers. However, interpretation of FRA signature still needs expert opinions and there is no FRA interpretation code generally accepted. Various mechanical faults with different extents on power transformers are required to aid FRA interpretation. To address this challenge, in...
متن کاملFEM based Reactance Computation for Transformer Winding Deformation Detection
Leakage reactance is one of the most important specifications in transformer that has significant impact on its overall design. Variation in leakage reactance serves as a diagnostic measure to indicate mechanical integrity of power transformers before and after a short circuit test that demonstrates mechanical strength of transformer windings. This paper presents an approach for leakage reactan...
متن کاملA Feasible Solution to Distinguish the Transformer Winding Deformation from Insulation Characteristic Impacts on FRA Spectrum
Frequency Response Analysis (FRA) is popular technique which has been used since the last decade as a diagnostic method for transformers. However, accurate interpretation of FRA measurements is still challenging. Recent studies reveal that apart from winding deformation, FRA data can also be influenced by moisture variation in transformer paper insulation. Hence, a specific transformer’s model ...
متن کاملCharacterization of Power Transformer Electromagnetic Forces Affected by Winding Faults
Electromagnetic forces in power transformer windings are produced by interaction between the leakage fluxes and current passing them. Since the leakage flux distribution along the windings height is in two axial and radial directions, so the electromagnetic forces have two components, radial and axial. There is a risk that a large electromagnetic force due to the short circuit or inrush current...
متن کامل