Modeling Particle Deposition on the Surfaces around a Multi-Slot Diffuser
نویسندگان
چکیده
Enhanced soiling on the wall/ceiling around a diffuser due to particle deposition is very unsightly and reduces our quality of life. This study aimed to model the particle deposition on the surfaces around multi-slot diffusers, which are widely used in transportation vehicles. An SST k-ω model with a modified Lagrangian method was proposed and validated with experimental data on particle deposition rate from the literature. This investigation then conducted chamber tests to qualitatively validate model’s ability to predict the deposition distribution around a multi-slot diffuser. Using the validated model, this study numerically investigated the effects of slot setting, supply air angle, and temperature differential on particle deposition around a multi-slot diffuser. The results indicated that, with the same supply airflow rate, increasing the area ratio of openings to bars in a multi-slot diffuser can reduce the particle deposition. When the angle between the supply air jet and the wall was increased to more than 45o, the particle deposition was significantly reduced. Furthermore, the impact of thermophoresis on particle deposition around a multi-slot diffuser was negligible.
منابع مشابه
modeling of controlled particle deposition on to electronically conducting surfaces
<span style="font-family: MSTT31c3f700; font-size...
متن کاملConvective Heat Transfer in Rooms with Ceiling Slot Diffusers (RP-1416)
Convection at interior surfaces significantly affects the overall heat transfer in office buildings with large glazing areas. While a large number of these office buildings utilize ceiling slot diffusers at the glazed building perimeter, convection correlations specific to these diffusers have not yet been investigated. This paper describes convection correlations developed for ceiling slot dif...
متن کاملComparison of Operating Room Ventilation Systems in the Protection of the Surgical Site
This paper uses airflow modeling and particle-tracking methodologies to compare the risk of contaminant deposition on an operating room (OR) surgical site and back table for different ventilation systems. The ventilation system designs considered incorporated commonly used diffuser types, in particular, conventional, laminar, nonaspirating, and displacement diffuser types. Further, a range of d...
متن کاملاثر فاصله شکاف از دماغه آبشکن مثلثی بر الگوی فرسایش و رسوب
Scour around structures in the river is the most destructivr factor of these structures. Therefore, different methods have been studied to reduce it. A creation slot is one of these methods in the suitable position that can be modified to control the flow pattern scour. In this study, the effects of using two parallel chord rectangular slots in the single spur dike with the opening of the eff...
متن کاملNumerical Simulation and Optimization Design of the Annular Mechanical Foam Breaker
The annular foam breaker is one which uses the vacuum and shear force generated by the Coanda effect to break foam. The pressure distribution directly affects its performance. So an investigation on the flow characteristics inside the annular foam breaker is important to optimize its structure. In this paper, the computational fluid dynamics (CFD) code, FLUENT, is employed to simulate the flow ...
متن کامل