Experimental Evaluation of Rogowski Coil Performance for Locating PD in Energized Overhead Covered-Conductor Feeder
نویسندگان
چکیده
An experimental analysis is performed to evaluate Rogowski coil performance for PD (partial discharge) location on overhead CC (covered-conductor) distribution lines. The measuring set-up is arranged in high voltage laboratory. A multi-end measuring method is chosen as a technique to locate PD source point on the line. A power transformer is used to energize one end of the CC line by the AC voltage source. The performance of Rogowski-coil is tested in noisy environment. The tests are carried out concerning different measurement conditions such as off-line and on-line PD measuring systems. The results obtained from the laboratory measurements confirm the capability of the Rogowski-coil in order to measure and locate the high frequency PD source on the CC line in consistent with energizing AC source. Chirp detector is used as a signal-processing tool in order to extract the PD signals and then apply the locator algorithm.
منابع مشابه
Modeling of Rogowski Coil for On-line Pd Monitoring in Covered- Conductor Overhead Distribution Networks
In this paper, EMTP/ATP simulation environment is used to model the Rogowski coil for partial discharge (PD) monitoring due to leaning trees on the covered-conductor (CC) overhead distribution lines. The simulations are performed to obtain the Rogowski coil response at different lengths of the CC line and the results are compared with those obtained from the laboratory measurements. The results...
متن کاملPartial Discharge Location Technique for Covered-Conductor Overhead Distribution Lines
Aalto University, P.O. Box 11000, FI-00076 Aalto www.aalto.fi Author Muzamir Isa Name of the doctoral dissertation Partial Discharge Location Technique for Covered-Conductor Overhead Distribution Lines Publisher School of Electrical Engineering Unit Department of Electrical Engineering Series Aalto University publication series DOCTORAL DISSERTATIONS 9/2013 Field of research Power Systems and H...
متن کاملEffects of Rogowski Coil and Covered-conductor Parameters on the Performance of Pd Measurements in Overhead Distribution Networks
An on-line single-phase partial discharge (PD) measuring system using Rogowski coil is simulated in EMTP/ATP for the monitoring of falling trees on coveredconductor (CC) overhead distribution lines. The simulation results are compared with those obtained from the laboratory measurements. The effect of Rogowski coil terminating impedance is analysed for the performance of PD measuring system. Th...
متن کاملDesign Modification of Rogowski Coil for Current Measurement in Low Frequency
The principle object of this paper is to offer a modified design of Rogowski coil based on its frequency response. The improvement of the integrator circuit for nullifying the phase difference between the waveforms of the measured-current and the corresponding terminal voltage is a further object of this investigation. This paper addresses an accurate, yet more efficient measuring and protect...
متن کاملA Novel Transient Fault Current Sensor Based on the PCB Rogowski Coil for Overhead Transmission Lines
The accurate detection of high-frequency transient fault currents in overhead transmission lines is the basis of malfunction detection and diagnosis. This paper proposes a novel differential winding printed circuit board (PCB) Rogowski coil for the detection of transient fault currents in overhead transmission lines. The interference mechanism of the sensor surrounding the overhead transmission...
متن کامل