Partial discharges (PD) are recognized as the main cause of the inner insulation deterioration process in power transformers. Therefore, the optimum inner insulation design is one of the challenges a transformer designer is faced with. Transformer strength, especially during transient conditions, is a criterion for transformer insulation designers. This challenge has made designers initiate and employ other types of winding, for example, rather than ordinary layer and disc windings employ the multiple-α windings. Multiple-α windings have a more complicated structure and are comprised of various parts with different physical structures and electrical characteristics. Typical partial discharge signals cover a wide frequency range from DC up to hundreds of MHz and different frequency components propagate through the winding depending upon the winding structure in different modes. Partial discharge propagation in single-α winding is more predictable compared to multiple-α winding. A 66 kV / 25 MVA interleaved winding, which has 19 fully interleaved discs, plays the role of a single-α winding. When this main winding is connected to the tap winding with a different structure and magnitude response, a multiple-α winding is constructed. Two terminal current signals are detected by the application of two homemade high frequency current transformers (HF-CT). The signals were amplified and fed into a 500 MHz digital storage oscilloscope. Home-made sensors are designed to provide maximum sensitivity in the desired frequency range. In order to evaluate the partial discharge signal accurately, a method for selecting the optimal wavelet is introduced to reduce the noise effects. This method is based on the capability of the chosen mother wavelet for generating coefficients with maximal values. The wavelet based de-noising method proposed can be employed in extracting the PD pulses from the measured signal successfully to provide enhanced information and further infer the original site of the PD pulse through the capacitive ratio method.. Keywords– Power transformer, partial discharge, wavelet analysis, PD location, PD propagation, multiple-α winding, single-α winding
منابع مشابه
Lumped Parameter Model for High Frequency Partial Discharge Estimation in High Voltage Transformer
Lumped Parameter Model is well known in solving high frequency signal propagation in high voltage transformer windings. At Southampton University, the modelling technique has been improvised and employed to solve partial discharge (PD) problem occurred within deep inside transformer windings. Firstly, a lumped capacitive parameter model was considered and secondly a transmission line lumped par...
متن کاملEvaluating the Improvement of Partial Discharge Localization Accuracy Using Frequency Response Assurance Criterion
Partial Discharge (PD) is the most important source of insulation degradation in power transformers. In order to prevent catastrophic failures in transformers, PDs need to be located as soon as possible so that maintenance measures can be taken in time. Due to the structural complexity of windings, locating the PD source inside a transformer winding is not a simple task. In this paper, the effi...
متن کاملPartial Discharge Location within a Transformer Winding Using Principal Component Analysis
Partial discharge (PD) may occur in a transformer winding due to ageing processes, operational over stressing or defects introduced during manufacture. The presence of PD does not necessarily indicate imminent failure of the transformer but it will lead to serious degradation and ageing mechanisms which can be considered as a precursor of transformer failure. A necessary step is required in ord...
متن کاملA Novel Transformer-Based Single-to-Three Phase Conversion Technique Using Rotating Magnetic Field Theory
This paper presents a new single to three phase converter using rotating magnetic field transformer. Conventional transformers have been used in many converters aiming at supplementary improvements and they usually have no critical effect on the conversion technique. In this paper, the conversion technique is based on a special rotating magnetic field transformer in which there are two windings...
متن کاملFuture template numerical interpretation techniques for PD pulse location in transformer windings
Identification and location of partial discharge (PD) source is an important diagnostic tool for reliable operation of transformer. In this paper, future template numerical interpretation techniques are proposed for location of PD pulse duration from 0.1 s to 5 s in transformer windings using sweep frequency response analysis (SFRA) principle. To analyze the efficacy of the proposed techniques ...
متن کامل