A Novel Neural Network Vector Control for Single-Phase Grid-Connected Converters with L, LC and LCL Filters
نویسندگان
چکیده
Abstract: This paper investigates a novel recurrent neural network (NN)-based vector control approach for single-phase grid-connected converters (GCCs) with L (inductor), LC (inductor-capacitor) and LCL (inductor-capacitor-inductor) filters and provides their comparison study with the conventional standard vector control method. A single neural network controller replaces two current-loop PI controllers, and the NN training approximates the optimal control for the single-phase GCC system. The Levenberg–Marquardt (LM) algorithm was used to train the NN controller based on the complete system equations without any decoupling policies. The proposed NN approach can solve the decoupling problem associated with the conventional vector control methods for L, LC and LCL-filter-based single-phase GCCs. Both simulation study and hardware experiments demonstrate that the neural network vector controller shows much more improved performance than that of conventional vector controllers, including faster response speed and lower overshoot. Especially, NN vector control could achieve very good performance using low switch frequency. More importantly, the neural network vector controller is a damping free controller, which is generally required by a conventional vector controller for an LCL-filter-based single-phase grid-connected converter and, therefore, can overcome the inefficiency problem caused by damping policies.
منابع مشابه
The Design of a New Double Loop Controller For Simultaneous Adjustment of Input and Output Voltages of Single-Phase Grid-Connected Inverter
Although LCL filters are used widely in the grid connected inverters to reduce high-orderharmonics, such a system increases system order and therefore sustainable design of closed-loopcontroller system will be complicated. Recently, the single-loop control strategy has beensuggested for L or LC filter based grid-connected inverters. However, the use of single-loopcontrol directly in LCL filter-...
متن کاملA Novel Control Strategy for a Single-phase Grid-connected Power Injection System
In this paper, a novel and simple control strategy, based on state feedback method is suggested to control the power injection system (PIS). The considered PIS is composed of, a DC voltage source, a voltage source inverter (VSI) and a L-C-L filter. The DC source includes the battery source with boosted voltage. The battery can be charged with photovoltaic cells. Since, the grid voltage acts as ...
متن کاملDesign of a Digital Voltage Controller in Single-Phase Grid-Connected Renewable Converters
Power decoupling of pulsating grid side power from constant source side power is one of the paramount issues in single phase-phase grid-connected renewable systems. The principal aim of such systems is the decrease of the capacitance of the decoupled capacitor. However, this causes some problems such as an increase in the total harmonic distortion (THD) of injected current to the grid and bus v...
متن کاملModeling and Control of Voltage Source Converters Connected to the Grid
This thesis deals with the modeling and control of pulse width modulated (PWM) voltage source converters connected to the grid. When voltage source converters are connected to the grid, the power quality and the dynamic performance are affected by the line filter connected between the converter and the grid, and by nonlinearities caused by the switching converter. In the thesis, the dynamic per...
متن کاملStability Improvement of Grid-connected Converter with LCL Filter based on Capacitor Current Active Damping by Computational Delay Reduction
Nowadays, LCL filters utilization to suppress the grid-connected inverter switching harmonics is expanding and various methods such as capacitor current active damping scheme could be investigated to damp out these harmonics. However, the computational delays including control system, and PWM switching delays have significant effect on damping system stability. In most of LCL filter parameter d...
متن کامل