An Improved Proportional Quasi-Resonant Control of Wind Power GCI under Unbalanced Grid Conditions
نویسندگان
چکیده
with conventional control strategy under unbalanced grid conditions, power fluctuations will be generated in the input active power and reactive power of the wind power Grid Connected Inverter (GCI). In this paper, a novel sequence extraction method is proposed in the voltage components decomposition. Based on second order generalized integrator (SOGI) with PLL, a decomposition module with an ability of frequency adaptation is built up, called FA-SOGI. To avoid the sequence extraction of grid current, a novel proportional quasi-resonant controller implemented also by FA-SOGI within αβ stationary coordinate system is introduced to improve innerloop current control performance. With two objectives of active power fluctuation suppression and reactive power fluctuation suppression, the proposed strategy is verified by simulation and experiment. The results show that the sequence decomposition module is correct and the power fluctuations can be obviously suppressed and DC-bus voltage can be steady. Key-Words: proportional quasi-resonant (PQR), power fluctuations, unbalanced grid, grid connected inverter (GCI), second order generalized integrator with frequency adaptation (FA-SOGI)
منابع مشابه
Sliding-Mode-based Improved Direct Active and Reactive Power Control of Doubly Fed Induction Generator under Unbalanced Grid Voltage Condition
This paper proposes an improved direct active and reactive power control (DPC) strategy for a grid-connected doubly fed induction generator (DFIG) based wind-turbine system under unbalanced grid voltage condition. The method produces required rotor voltage references based on the sliding mode control (SMC) approach in stationary reference frame, without the requirement of synchronous coordinate...
متن کاملLow Voltage Ride Through Enhancement Based on Improved Direct Power Control of DFIG under Unbalanced and Harmonically Distorted Grid Voltage
In the conventional structure of the wind turbines along with the doubly-fed induction generator (DFIG), the stator is directly connected to the power grid. Therefore, voltage changes in the grid result in severe transient conditions in the stator and rotor. In cases where the changes are severe, the generator will be disconnected from the grid and consequently the grid stability will be attenu...
متن کاملReactive and Active Power Control of Grid WECS Based on DFIG and Energy Storage System under both Balanced and Unbalanced Grid Conditions
This paper focuses on improving the active and reactive power control of Wind Energy Conversion System (WECS) by employing the Battery Energy Storage System (BESS) and controlling the frequency and voltage regulation instantaneously. The proposed power control scheme is composed of two control loops so that they are implemented and designed for active power control and controlling the reactive ...
متن کاملAn improved synchronous reference frame current control strategy for a photovoltaic grid-connected inverter under unbalanced and nonlinear load conditions
In recent years, renewable energy sources have been considered the most encouraging resources for grid and off-grid power generation. This paper presents an improved current control strategy for a three-phase photovoltaic grid-connected inverter (GCI) under unbalanced and nonlinear load conditions. It is challenging to suppress the harmonic content in the output current below a pre-set value in...
متن کاملAn Optimal Integrated Control Scheme for Permanent Magnet Synchronous Generator-Based Wind Turbines under Asymmetrical Grid Fault Conditions
Abstract: In recent years, the increasing penetration level of wind energy into power systems has brought new issues and challenges. One of the main concerns is the issue of dynamic response capability during outer disturbance conditions, especially the fault-tolerance capability during asymmetrical faults. In order to improve the fault-tolerance and dynamic response capability under asymmetric...
متن کامل