Determination of Ignitable Liquids in Fire Debris: Direct Analysis by Electronic Nose
نویسندگان
چکیده
Arsonists usually use an accelerant in order to start or accelerate a fire. The most widely used analytical method to determine the presence of such accelerants consists of a pre-concentration step of the ignitable liquid residues followed by chromatographic analysis. A rapid analytical method based on headspace-mass spectrometry electronic nose (E-Nose) has been developed for the analysis of Ignitable Liquid Residues (ILRs). The working conditions for the E-Nose analytical procedure were optimized by studying different fire debris samples. The optimized experimental variables were related to headspace generation, specifically, incubation temperature and incubation time. The optimal conditions were 115 °C and 10 min for these two parameters. Chemometric tools such as hierarchical cluster analysis (HCA) and linear discriminant analysis (LDA) were applied to the MS data (45-200 m/z) to establish the most suitable spectroscopic signals for the discrimination of several ignitable liquids. The optimized method was applied to a set of fire debris samples. In order to simulate post-burn samples several ignitable liquids (gasoline, diesel, citronella, kerosene, paraffin) were used to ignite different substrates (wood, cotton, cork, paper and paperboard). A full discrimination was obtained on using discriminant analysis. This method reported here can be considered as a green technique for fire debris analyses.
منابع مشابه
Achieving a Near-Theoretical Maximum in Peak Capacity Gain for the Forensic Analysis of Ignitable Liquids Using GCGC-TOFMS
At present, gas chromatography–quadrupole mass spectrometry (GC-qMS) is considered the gold standard amongst analytical techniques for fire debris analysis in forensic laboratories worldwide, specifically for the detection and classification of ignitable liquids. Due to the highly complex and unpredictable nature of fire debris, traditional one-dimensional GC-qMS often produces chromatograms th...
متن کاملBest Practices for the Interpretation and Use of the Weathered and Biologically Degraded Samples in the Ignitable Liquid Database
Biologically Degraded Samples in the Ignitable Liquids Database The Ignitable Liquids Reference Committee of the Technical and Scientific Working Group for Fire and Explosions has prepared the following guide so users of the database are aware of the considerations and limitations of the weathered and biologically degraded samples contained within the ignitable liquids database. The guide descr...
متن کاملAnalysis of arson fire debris by low temperature dynamic headspace adsorption porous layer open tubular columns.
In this paper we present results of the application of PLOT-cryoadsorption (PLOT-cryo) to the analysis of ignitable liquids in fire debris. We tested ignitable liquids, broadly divided into fuels and solvents (although the majority of the results presented here were obtained with gasoline and diesel fuel) on three substrates: Douglas fir, oak plywood and Nylon carpet. We determined that PLOT-cr...
متن کاملA study of the effects of a Micelle Encapsulator Fire Suppression Agent on dynamic headspace analysis of fire debris samples.
The effects of a Micelle Encapsulator Fire Suppression Agent (F-500, Hazard Control Technologies Inc., Fayetteville, Georgia) on the routine analysis of fire debris samples by Gas Chromatography (GC) were studied. When mixed with water the product can be used in the suppression of Class A and Class B fires. Laboratory tests were performed to determine whether or not the product has any effect o...
متن کاملExtraction and concentration of vapors from fire debris for forensic purposes: evaluation of the use of Radiello Passive Air Sampler.
The Radiello Passive Air Sampler is one of the latest innovations developed for the sampling of pollutants in the air by passive headspace. It has been reported that its properties allow an enhanced sensitivity, reproducibility and adsorption capacity. It therefore appears to be of interest in the extraction of potential residues of ignitable liquids present in fire debris when arson is suspect...
متن کامل