چکیده

Grid disturbances, especially grid faults, have very unfavorable effect on the performance of wind turbine based Doubly Fed Induction Generator (DFIG). In this study active and reactive powers control of DFIG with STATCOM has been carried out to improve Fault Ride Through (FRT) capability of a wind turbine. In order to excel improvement of the DFIG behavior under grid fault disturbances, an optimized crowbar protection method is also considered together with STATCOM. The optimized protection crowbar resistance is achieved through Analytical Hierarchy Process (AHP) algorithm. Simulations results illustrate that an optimized crowbar protection method along with STATCOM has improved the stability of wind farm and provide grid code requirement compared with that of methods without using the optimized crowbar resistance.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Wind Turbine Control Design to Enhance the Fault Ride- Through Capability

This paper presents a control strategy for wind turbines to enhance their fault ride-through capability. The controller design is based on pitch controlled variable speed wind turbine equipped with doubly-fed induction generator (DFIG). The fault ride-through is realized by injecting a crowbar with variable resistance on the generator rotor circuit. To reduce the mechanical loads induced by gri...

متن کامل

Analyzing the Application of Crowbar And Statcom To Overcome Voltage Sags With Actual Field Data

Wind power generation is increasing rapidly in India and wind integration with the grid is considered as a promising source of energy, Double Fed Induction Generator (DFIG) being the most commonly used wind turbine generator, when integrated with the grid show challenges during grid faults. This paper focuses on the challenges faced by DFIG during the occurrence of voltage sags and the Low Volt...

متن کامل

Low Voltage Ride Through Enhancement Based on Improved Direct Power Control of DFIG under Unbalanced and Harmonically Distorted Grid Voltage

In the conventional structure of the wind turbines along with the doubly-fed induction generator (DFIG), the stator is directly connected to the power grid. Therefore, voltage changes in the grid result in severe transient conditions in the stator and rotor. In cases where the changes are severe, the generator will be disconnected from the grid and consequently the grid stability will be attenu...

متن کامل

Low Voltage Ride through Capability Improvement of Dfig Based Wind Turbine Using Statcom

This paper studies a control strategy to improve low voltage ride through (LVRT) capability of doubly fed induction generator (DFIG)-based wind turbine (WT). This solution is based on the DFIG with Crowbar circuit control and the installation of STATCOM which is connected at the point of common coupling (PCC). The simulation model of WTs with STATCOM is built using the environment MATLAB/Simuli...

متن کامل

Enhancement of Fault Ride through Capability of a Wind Driven Dfig Connected to the Grid

Enhancement of fault ride-through (FRT) capability and subsequent improvement of rotor speed stability of wind farms equipped with doubly fed induction generator (DFIG) is the objective of this paper. The objective is achieved by employing a novel FRT scheme with suitable control strategy. The proposed FRT scheme, which is connected between the rotor circuit and dc link capacitor in parallel wi...