Rapid Reserve Generation from a Francis Turbine for System Frequency Control
نویسندگان
چکیده
The increase in contributions from non base load renewables, such as wind and solar, can have adverse effects on the stability of an electrical grid. In this study, the possibility of rapidly loading a Francis turbine from a tail water depression (TWD) mode for providing additional system frequency control is investigated. Based on the analysis of full-scale TWD test results and key findings from the transient testing of a micro-hydro scale turbine unit, a detailed description of the TWD transition process is given. The formulation of an improved turbine model for use in one-dimensional hydro-electric plant models is presented with simulation results compared to full-scale data. The analytical model, which calculates output power according to the conservation of angular momentum and identified sources of loss, is used in parallel with full-scale and model scale test observations to elucidate the events and mechanisms occurring during this proposed transition. The output response, in terms of active power, was found to be highly dependent on guide vane opening rate in both full-scale and model tests. For an approximate doubling in opening rate, the duration of the reverse power flow was reduced by 38% and 21%, for full-scale and model units, while the low pressure transient increased by 16% and 8%, respectively. The analytical model was shown to capture the general response characteristic in all cases tested; however, output power response was over predicted due to two identified model assumptions made, while, for the more rapid opening, the penstock pressure was under predicted by approximately 15%.
منابع مشابه
Analysis of Wind Speed Forecasting Error Effects on Automatic Generation Control Performance
The main goal of this paper is to study statistical indices and evaluate AGC indices in power system which has large penetration of the WTGs. Increasing penetration of wind turbine generations, needs to study more about impacts of it on power system frequency control. Frequency control is changed with unbalancing real-time system generation and load . Also wind turbine generations have more flu...
متن کاملبرنامهریزی همزمان انرژی و ذخیره کنترل فرکانس اولیه با لحاظ کردن قابلیتهای فنی واحدهای نیروگاهی پیشرفته
Load frequency control includes the operating system and functions that provide real time balance of load and generation. On the other hand, depending on technical capabilities and operational constraints, generating units may be classified for participating in frequency control. Simultaneous scheduling of generation together with primary reserve, in market based power system, has been investig...
متن کاملFrequency Control of an Islanded Microgrid based on Intelligent Control of Demand Response using Fuzzy Logic and Particle Swarm Optimization (PSO) Algorithm
Due to the increasing penetration of renewable energies in the power system, the frequency control problem has attracted more attention, while the traditional control methods are not capable of regulating the frequency and securing the stability of the system. In smart grids, demand response as the frequency control tool reduces the dependence on spinning reserve and high cost controllers. In a...
متن کاملControl Reconfiguration of a Boiler-Turbine Unit After Actuator Faults
Boiler-turbines are one of the most important parts in power generation plants. The safety problem in such systems has always been a special concern. This paper discusses the application of control reconfig uration by fault-hiding approach for a boiler-turbine unit. In Fault-hiding approach, after occurrence of a fault, nominal controller of the system remains unchanged; instead, a reconfigurat...
متن کاملFuzzy Based Load-frequency Control in an Interconnected Power System with Wind Turbine
It’s important to realize, optimized dispatching of generating units would be useless without a method of control. Frequency regulation in interconnected network is one of the main challenges posed by wind turbine in modern power system. Obviously the method of load frequency control (LFC) plays a vital role in large interconnected power system. However the modern LFC should be able to handle c...
متن کامل