Analysis of SLF Interruption Performance of Self-Blast Circuit Breaker by Means of CFD Calculation
نویسندگان
چکیده
This paper presents the performance analysis results of a short line fault interruption of a gas circuit breaker, particularly a self-blast type breaker. Hot gas flow analysis was carried out using a CFD calculation combined with the arc model and nozzle ablation. To evaluate the interruption performance, the index function was defined using the pressure in the heating chamber and the density above the arc region. The simulation and test results showed that the gas flow field and suitable choice of an interruption performance index can be used to predict the interruption characteristics and provide guidelines for designing self-blast breakers with a higher interruption capability.
منابع مشابه
Analysis of Electric Field and Polarization of SF6 Circuit Breaker to Approach a Suitable Structure
Abstract: The application of electric field theory to widely different aspects of electrical insulation has led to more understanding the phenomena. Electric fields may be considered as the main reason for insulation failure. The purpose of this paper is to modify importance of analyzing electric field in insulation design. The SF6 circuit breaker is chosen as case study that encounters cri...
متن کاملVarious Types of Circuit Breakers used in Power System for Smooth Working of the Transmission Line
Once a power system is established it is necessary to protect it from faults (whether internal or external). So we use some protecting and sensing device like circuit breakers, Relays, Fuses etc. Circuit breaker is a mechanical device capable of making, carrying and breaking currents under normal circuit conditions and also making, carrying for a specified time. This paper represents informatio...
متن کاملNumerical Simulation and Optimization Design of the Annular Mechanical Foam Breaker
The annular foam breaker is one which uses the vacuum and shear force generated by the Coanda effect to break foam. The pressure distribution directly affects its performance. So an investigation on the flow characteristics inside the annular foam breaker is important to optimize its structure. In this paper, the computational fluid dynamics (CFD) code, FLUENT, is employed to simulate the flow ...
متن کاملApproaching the Processes in the Generator Circuit Breaker at Disconnection through Sustainability Concepts
Nowadays, the electric connection circuits of power plants (based on fossil fuels as well as renewable sources) entail generator circuit-breakers (GCBs) at the generator terminals, since the presence of that electric equipment offers many advantages related to the sustainability of a power plant. In an alternating current (a.c.) circuit the interruption of a short circuit is performed by the ci...
متن کاملIntegrated Preventive and Predictive Maintenance Markov Model for Circuit Breakers Equipped With Condition Monitoring
The Circuit Breaker (CB) is one of the most important equipment in power systems. CB must operate reliably to protect power systems as well as to perform tasks such as load disconnection, normal interruption, and fault current interruption. Therefore, the reliable operation of CB can affect the security and stability of power network. In this paper, effects of Condition Monitoring (CM) of CB on...