Using SF6 Decomposed Component Analysis for the Diagnosis of Partial Discharge Severity Initiated by Free Metal Particle Defect

نویسندگان

  • Ju Tang
  • Xu Yang
  • Dong Yang
  • Qiang Yao
  • Yulong Miao
  • Chaohai Zhang
  • Fuping Zeng
چکیده

The decomposition characteristics of a SF6 gas-insulated medium were used to diagnose the partial discharge (PD) severity in DC gas-insulated equipment (DC-GIE). First, the PD characteristics of the whole process were studied from the initial PD to the breakdown initiated by a free metal particle defect. The average discharge magnitude in a second was used to characterize the PD severity and the PD was divided into three levels: mild PD, medium PD, and dangerous PD. Second, two kinds of voltage in each of the above PD levels were selected for the decomposition experiments of SF6. Results show that the negative DC-PD in these six experiments decomposes the SF6 gas and generates five stable decomposed components, namely, CF4, CO2, SO2F2, SOF2, and SO2. The concentrations and concentration ratios of the SF6 decomposed components can be associated with the PD severity. A minimum-redundancy-maximum-relevance (mRMR)-based feature selection algorithm was used to sort the concentrations and concentration ratios of the SF6 decomposed components. Back propagation neural network (BPNN) and support vector machine (SVM) algorithms were used to diagnose the PD severity. The use of C(CO2)/CT1, C(CF4)/C(SO2), C(CO2)/C(SOF2), and C(CF4)/C(CO2) shows good performance in diagnosing PD severity. This finding serves as a foundation in using the SF6 decomposed component analysis (DCA) method to diagnose the insulation faults in DC-GIE and assess its insulation status.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Correlation Characteristics Comparison of SF6 Decomposition versus Gas Pressure under Negative DC Partial Discharge Initiated by Two Typical Defects

Aimed to clarify the correlation characteristics between the internal partial discharge (PD) in negative direct current (DC) gas insulated system (GIS) and gas pressure initiated by two typical defects (i.e., free-metal particles and metal protrusion), this study on PD decomposition of sulfur hexafluoride (SF6) was investigated under different pressures on the basis of constructing a SF6 decomp...

متن کامل

Decomposition Characteristics of SF6 and Partial Discharge Recognition under Negative DC Conditions

Four typical types of artificial defects are designed in conducting the decomposition experiments of SF6 gas to obtain and understand the decomposition characteristics of SF6 gas-insulated medium under different types of negative DC partial discharge (DC-PD), and use the obtained decomposition characteristics of SF6 in diagnosing the type and severity of insulation fault in DC SF6 gas-insulated...

متن کامل

Adsorption of SF6 decomposed gas on anatase (101) and (001) surfaces with oxygen defect: A density functional theory study

The detection of partial discharge by analyzing the components of SF6 gas in gas-insulated switchgears is important to the diagnosis and assessment of the operational state of power equipment. A gas sensor based on anatase TiO2 is used to detect decomposed gases in SF6. In this paper, first-principle density functional theory calculations are adopted to analyze the adsorption of SO2, SOF2, and ...

متن کامل

The SF6 Decomposition Mechanism: Background and Significance

Gas Insulated Switchgear (GIS) has been widely used in substations. The insulating medium used in GIS is sulfur hexafluoride (SF6) gas. However, the internal insulation defect existed in GIS would inevitably lead to partial discharge (PD), and cause the composition of SF6 to SOF2, SO2F2 and SO2 and other characteristic component gases. The decomposition phenomenon would greatly reduce the insul...

متن کامل

Study on the Characteristic Decomposition Components of DC SF6-Insulated Equipment under Positive DC Partial Discharge

Pulses with different amplitudes occur when an inner partial discharge fault exists in SF6-gas-insulated DC high-voltage electrical equipment. SF6 decomposes following complex physical and chemical processes. Discussing and quantifying the mathematical relationship of pulse discharge quantities to SF6 decomposition component characteristics is helpful to evaluate and predict the insulation faul...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2017