Firing Angle Range Control For Minimising Harmonics in TCR Employed in SVC-s

ثبت نشده
چکیده

Most electrical distribution systems are incurring large losses as the loads are wide spread, inadequate reactive power compensation facilities and their improper control. A typical static VAR compensator consists of capacitor bank in binary sequential steps operated in conjunction with a thyristor controlled reactor of the smallest step size. This SVC facilitates stepless control of reactive power closely matching with load requirements so as to maintain power factor nearer to unity. This type of SVC’s requiring a appropriately controlled TCR. This paper deals with an air cored reactor suitable for distribution transformer of 3phase, 50Hz, Dy11, 11KV/433V, 125 KVA capacity. Air cored reactors are designed, built, tested and operated in conjunction with capacitor bank in five binary sequential steps. It is established how the delta connected TCR minimizes the harmonic components and the operating range for various electrical quantities as a function of firing angle is investigated. In particular firing angle v/s line & phase currents, D.C. components, THD’s, active and reactive powers, odd and even triplen harmonics, dominant characteristic harmonics are all investigated and range of firing angle is fixed for satisfactory operation. The harmonic spectra for phase and line quantities at specified firing angles are given. In case the TCR is operated within the bound specified in this paper established through simulation studies are yielding the best possible operating condition particularly free from all dominant harmonics. Keywords—Binary Sequential switched capacitor bank, TCR, Nontriplen harmonics, step less Q control, Active and Reactive power, Simulink

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Investigation of Effect of Harmonics on Voltage Stability in a Grid System by SVC

This paper investigates the role of Static Var Compensator (SVC) on stability of voltage in grid system due to the presence of harmonics.. Here the design of SVC is based on the combination of Thyristor switched capacitors (TSC’s) and Thyristor controlled reactor (TCR) . TSC’s are used for switching the capacitor banks on and off while the TCR continuously controls the reactive power by varying...

متن کامل

An Innovative TCR Compensator for Closed Loop Reactive Power Compensation of Dynamic Loads

Topology for closed loop reactive power compensation suitable for dynamic loads using TCR is presented. Firing angle range of TCR is selected in such a way to keep the harmonic content at a minimum level. Simulation results show that the proposed scheme can achieve reactive power compensation in less than a half cycle and the harmonics contents of source are maintained at insignificant levels d...

متن کامل

Selective Harmonics Elimination Technique in Cascaded H-Bridge Multi-Level Inverters Using the Salp Swarm Optimization Algorithm

A new optimization method is proposed in this paper for finding the firing angles in multi-level voltage source inverters to eliminate low-order selective harmonics and reduce total harmonic distortion (THD) value of the output voltage. For thid end, Fourier series is used for calculating objective function and selecting specific harmonics. Regarding the nature and complexity of the employed no...

متن کامل

New Methods for Harmonic Reduction in T. C. R. by Sequence Control of Transformer Taps

Thyristor controlled static compensators consist of two basic schemes, TCR and TSC. Owing to the discontinuous current in TCR, current harmonics are generated in the supply system. This paper introduces two methods for the reduction of these harmonics. On the basis of the coordination or uncoordination of turn ratios with harmonic reduction levels, each method is described in two alternative sc...

متن کامل

Voltage Stability Improvement using Static Var Compensator in Power Systems

This paper investigates the effects of Static Var Compensator (SVC) on voltage stability of a power system. The functional structure for SVC built with a Thyristor Controlled Reactor (TCR) and its model are described. The model is based on representing the controller as variable impedance that changes with the firing angle of the TCR. A Power System Computer Aided Design /Electromagnetic Transi...

متن کامل

ذخیره در منابع من


  با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

عنوان ژورنال:

دوره   شماره 

صفحات  -

تاریخ انتشار 2012