Control of airborne infectious diseases in ventilated spaces.
نویسنده
چکیده
We protect ourselves from airborne cross-infection in the indoor environment by supplying fresh air to a room by natural or mechanical ventilation. The air is distributed in the room according to different principles: mixing ventilation, displacement ventilation, etc. A large amount of air is supplied to the room to ensure a dilution of airborne infection. Analyses of the flow in the room show that there are a number of parameters that play an important role in minimizing airborne cross-infection. The air flow rate to the room must be high, and the air distribution pattern can be designed to have high ventilation effectiveness. Furthermore, personalized ventilation may reduce the risk of cross-infection, and in some cases, it can also reduce the source of infection. Personalized ventilation can especially be used in hospital wards, aircraft cabins and, in general, where people are in fixed positions.
منابع مشابه
Modelling the transmission of airborne infections in enclosed spaces.
The Wells-Riley equation for modelling airborne infection in indoor environments is incorporated into an SEIR epidemic model with a short incubation period to simulate the transmission dynamics of airborne infectious diseases in ventilated rooms. The model enables the effect of environmental factors such as the ventilation rate and the room occupancy to be examined, and allows the long-term imp...
متن کاملSystematic study of person-to-person contaminant transport in mechanically ventilated spaces (RP-1458)
Abstract It is essential to investigate person-to-person contaminant transport in mechanically ventilated spaces to improve air distribution design and reduce the infection risk from airborne infectious diseases. This paper provides a systematic study of the effects of ventilation mode, ventilation rate, and person-to-person distance on person-to-person contaminant transport. This study first c...
متن کاملIndoor Airborne Bio Aerosols in Valiasr Hospital in Zanjan, Iran
Background: Bio aerosols include airborne micro-organisms such as bacteria, fungi, viruses, etc and their products. Exposure to a bio aerosol is linked with a broad spectrum of health problems, including infectious diseases, acute toxic effects, allergies, and cancer. The aim of this study was to evaluate the quality and quantity of bio aerosols found in the air of different wards in Valiasr Ho...
متن کاملASHE Monograph
T his literature review explores the role that ventilation, assessed by air changes per hour (ACH), plays in infection transmission and disease control. The American Society of Heating, Refrigerating, and Air-Conditioning Engineers (ASHRAE) Position Document on Airborne Infectious Diseases (2009) notes the dilution effect that ACH has on infectious disease transmission. The Wells-Riley equation...
متن کاملFlow dynamics and characterization of a cough.
UNLABELLED Airborne disease transmission has always been a topic of wide interests in various fields for decades. Cough is found to be one of the prime sources of airborne diseases as it has high velocity and large quantity of droplets. To understand and characterize the flow dynamics of a cough can help to control the airborne disease transmission. This study has measured flow dynamics of coug...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- Journal of the Royal Society, Interface
دوره 6 Suppl 6 شماره
صفحات -
تاریخ انتشار 2009