The Applicability of Traditional Protection Methods to Lines Emanating from VSC-HVDC Interconnectors and a Novel Protection Principle

نویسندگان

  • Shimin Xue
  • Jingyue Yang
  • Yanxia Chen
  • Cunping Wang
  • Zhe Shi
  • Miao Cui
  • Botong Li
چکیده

Voltage source converter (VSC)-based high voltage direct current (VSC-HVDC) interconnectors can realize accurate and fast control of power transmission among AC networks, and provide emergency power support for AC networks. VSC-HVDC interconnectors bring exclusive fault characteristics to AC networks, thus influencing the performance of traditional protections. Since fault characteristics are related to the control schemes of interconnectors, a fault ride-through (FRT) strategy which is applicable to the interconnector operating characteristic of working in four quadrants and capable of eliminating negative-sequence currents under unbalanced fault conditions is proposed first. Then, the additional terms of measured impedances of distance relays caused by fault resistances are derived using a symmetrical component method. Theoretical analysis shows the output currents of interconnectors are controllable after faults, which may cause malfunctions in distance protections installed on lines emanating from interconnectors under the effect of fault resistances. Pilot protection is also inapplicable to lines emanating from interconnectors. Furthermore, a novel pilot protection principle based on the ratio between phase currents and the ratio between negative-sequence currents flowing through both sides is proposed for lines emanating from the interconnectors whose control scheme aims at eliminating negative-sequence currents. The validity of theoretical analysis and the protection principle is verified by PSCAD/EMTDC simulations.

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

ثبت نام

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Requirements for Fault Protection in HVDC Grids

Conventional Voltage Source Converters (VSC) cannot interrupt DC fault currents and DC circuit breakers are not yet commercially available for HVDC power ratings. Thus, the protection of VSC-HVDC systems is still an obstacle for the development of this technology. The features of VSC-HVDC systems make them suitable for implementing HVDC grids. Nevertheless, HVDC grids are more complex than poin...

متن کامل

Controlled Islanding with Vsc-hvdc Links Acknowledgements

Controlled islanding has been widely discussed in the literature as a novel concept for the power system protection. However, the islanding can result in unbalanced islands where the power mismatch will often cause an instability that can lead either to a subsequent load shedding or generator tripping within the islands. Controlled VSC-HVDC links can mitigate the negative consequences of the co...

متن کامل

Research of Bipolar HVDC Transmission Lines based on Traveling Wave Differential Protection

The principle of the traveling wave based differential protection for bipolar HVDC transmission lines is proposed in the paper. Unlike the traditional current differential protection, the quantity of current is replaced by the quantity of the traveling wave for comparison. The traveling wave at the remote end is transferred to the local end for comparison to the local traveling wave. For the bi...

متن کامل

Dynamic Harmonic Modeling and Analysis of VSC-HVDC Systems

Harmonics have become an important issue in modern power systems. The widespread penetration of non-linear loads to emerging power systems has turned power quality analysis into an important operation issue under both steady state and transient conditions. This paper employs a Dynamic Harmonic Domain (DHD) based framework for dynamic harmonic analysis of VSC-HVDC systems. These systems are wide...

متن کامل

Analysis and Improving Reliability Indices of VSC-HVDC transmission system tapped by a VSC- station

During the last three decades, reliability analysis of power systems considering transformers, breakers, transmission lines, and generators failure has been widely applied. This analysis has been done especially in the generation and transmission levels and is mainly restricted to high voltage alternating current (HVAC) systems. HVDC transmission systems are becoming increasingly popular when c...

متن کامل