Galvanic Coupling of Direct Currents in Transmission Grids and Its Effects on Power Transformers
نویسندگان
چکیده
Different stress factors impact power transformers during service. In most cases, the effects of additional direct current (DC) components are not taken into consideration. Nevertheless, this contribution considers DC or quasi-DC components which occur in the German transmission grid (400 kV level). Current measurements are therefore performed at several grounded star points of grid coupling power transformers using a customized current monitoring system. At a first glance, DC levels in the range of several Amperes can be observed. The subsequent detailed analysis allows discriminating different superimposing DC sources contributing to star points’ direct currents. The correlation of current measurements at different locations with the actual grid topology and switching operations enables the identification and localization of different sources. Additional comparisons to temporal changes within the earth’s magnetic field provide information about the impact of geomagnetically induced currents (GIC). The effects of observed direct currents on power transformers are determined by an evaluation of mechanical oscillations of affected transformers. The effects are linked to the transformer’s magnetic equivalent circuit and derived from half wave saturation effects of the magnetic hysteresis loop. A large-scaled laboratory setup which consists of two connected 380 kV / 110 kV, 350 MVA 5-limb power transformers is used to emulate DC effects and mechanical oscillations. Comparisons to field measurements are used to verify the model theory and the setup. In this context, the ability of low cost vibration measurement systems to detect direct currents in power transformers is also evaluated.
منابع مشابه
Betrachtung galvanisch eingekoppelter Gleichströme im Übertra- gungsnetz und deren Auswirkungen auf Leistungstransformatoren Galvanic DC coupling in transmission grids and its effects on power transformers
Power transformers are facing different stress factors during service. Usually, the effects of DC components superimposing AC phase currents are not taken into consideration. Nevertheless, DC can occur in transmission grids due to different sources. This contribution presents ongoing field measurements which show DC in the range of serval Amperes. Different superimposing DC sources are identifi...
متن کاملGalvanically Isolated Modular Converter
Direct current (DC) electrical grids are already a reality in low voltage (LV) telecom distribution systems and point-to-point high voltage DC transmission. Medium voltage (MV) domain, despite its big potential, still suffers from a lack of suitable conversion and protection technologies. This study presents a bidirectional, galvanically isolated, high power converter for interface of emerging ...
متن کاملمکانیابی خطا در خطوط انتقال با حضور محدودکننده جریان خطا
Fault location is an interesting subject in power grids. On the other hand, the application of fault current limiter (FCL) has been increasing in power network and causes some problems in operation of protection systems. This paper studies the application of FCL in power system and its effect on one-ended simple reactance fault location methods. In these methods, only voltages and currents of t...
متن کاملDiscrimination of Inrush from Fault Currents in Power Transformers Based on Equivalent Instantaneous Inductance Technique Coupled with Finite Element Method
The phenomenon of magnetizing inrush is a transient condition, which occurs primarily when a transformer is energized. The magnitude of inrush current may be as high as ten times or more times of transformer rated current that causes malfunction of protection system. So, for safe running of a transformer, it is necessary to distinguish inrush current from fault currents. In this paper, an equiv...
متن کاملArtificial Intelligence Based Approach for Identification of Current Transformer Saturation from Faults in Power Transformers
Protection systems have vital role in network reliability in short circuit mode and proper operating for relays. Current transformer often in transient and saturation under short circuit mode causes mal-operation of relays which will have undesirable effects. Therefore, proper and quick identification of Current transformer saturation is so important. In this paper, an Artificial Neural Network...