Acute aluminum encephalopathy in a dialysis center caused by a cement mortar water distribution pipe.
نویسندگان
چکیده
BACKGROUND In Curaçao, distilled seawater from the water plant was used without further purification for hemodialysis for several decades. A new distribution pipe supplying water to a dialysis center on the island was installed in May 1996. To protect it from corrosion, this pipe was lined on the inside with a cement mortar. Because of the aggressiveness of the distilled water, calcium and aluminum (Al) leached from the cement mortar into the water used to prepare dialysate. This caused a possible hard water syndrome and definite acute Al intoxication. METHODS We reviewed clinical details and outcome at follow-up, and arranged laboratory and toxicological studies of serum and hemodialysis water. RESULTS Of the 27 patients who had a similar exposure ( approximately 60 hours) to the contaminated dialysate, 10 died from acute Al encephalopathy, whereas 17 patients had no or only minor symptoms and survived. The nonsurvivors were older (64 +/- 3 years vs. 52 +/- 2 years, P < 0.01) and had a lower body weight (57.5 +/- 5.9 kg vs. 86.5 +/- 4.1 kg, P < 0.01) and lower serum albumin concentrations (33 +/- 1 vs. 36 +/- 1 g/L, P < 0.01). Anuria tended to be more common in the nonsurvivors (8 out of 10 vs. 8 out of 17, P> 0.05). Serum Al concentrations, available in seven nonsurvivors, were significantly higher than in the survivors (808 +/- 127 vs. 255 +/- 25 microg/L, P < 0.01). CONCLUSIONS The water distribution pipe was lined with a cement mortar that was probably inappropriate for transporting drinking water. Water distribution facilities as well as the dialysis community should be aware of the possibility of Al leaching from cemented water distribution pipes. Similar Al loads appear to induce a more severe intoxication in malnourished, older patients with smaller Al distribution volumes and anuria.
منابع مشابه
The effects of acid precipitation runoff episodes on reservoir and tapwater quality in an Appalachian Mountain water supply.
The aluminum concentration and Ryznar Index increased and the pH decreased in a small Appalachian water supply reservoir following acid precipitation runoff episodes. Concomitant increases in tapwater aluminum and decreases in tapwater pH were also observed at two homes in the water distribution system. Lead concentrations in the tapwater of one home frequently exceeded recommended levels, alth...
متن کاملALUMINUM TOXICITY: A REVIEW IN RELATION TO CHRONIC RENAL FAILURE PATIENTS M AINTAINED ON REGULAR HEMODIALYSIS
Aluminum is present in very small amounts in living organisms but abundant in the environment. A growing literature links with the biochemistry of aluminum and also with a series of diseases in chronic renal failure patients on treatment with hemodialysis. The initial description of potential aluminum toxicity in renal failure patients relates to description of dialysis encephalopathy syndr...
متن کاملEffect of a Carboxylic Acid on Rheological Properties of a High Alumina Cement Mortar
In this work, we studied the effect of carboxylic acid on the rheological properties of a high-alumina cement mortar (CH45) produced by the Algerian firm REFRACTAL.The investigated properties are setting time, water consumption, electrical conductivity, pH, density and the compressive strength. The results show a setting time of about 200 min for the acid...
متن کاملEngineering and operating approaches for controlling asbestos fibers in drinking water.
Techniques are available to minimize the concentration of asbestos fibers in drinking water. Filtration research conducted at locations on Lake Superior and in the Cascade Mountains in Washington has shown that amphibole and chrysotile fibers can be removed by granular media filtration. Removal percentages can exceed 99% when the raw water is coagulated properly and the filtered water turbidity...
متن کاملSpatial Distribution of Mechanical and Electrical Properties of Cement Mortar Prior to Loading
The hardness was found to be lower (by ;10 in Rockwell H scale) and the volume electrical resistivity was found to be higher (about doubled) at the edge (up to a depth of ;5 cm for curing at 100% relative humidity) than at the center of a cement mortar specimen prior to loading. This is attributed to the faster drying at the edge and the resulting poorer bond between cement paste and sand at th...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید
ثبت ناماگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید
ورودعنوان ژورنال:
- Kidney international
دوره 59 2 شماره
صفحات -
تاریخ انتشار 2001