A Closed-Loop Selective Harmonic Compensation for Active Filters
نویسنده
چکیده
This paper proposes a control algorithm for parallel active power filters, based on current-controlled pulsewidth-modulated converters, which allows precise compensation of selected harmonic currents produced by distorting loads. The approach is based on the measurement of line currents and performs the compensation of the selected harmonics using closed-loop synchronous frame controllers. Thanks to the closed-loop operation, full compensation of the desired harmonics is achieved even in the presence of a significant delay in the current control. Thanks to the selective approach, active filter interactions with possible dynamic components of the load are minimized. Moreover, the complexity of the synchronous frame controllers is overcome using equivalent stationary frame controllers. Experimental results confirm the theoretical expectations.
منابع مشابه
Indirect Control of Single-Phase Active Power Filters using Harmonic Control Arrays
The ever increase of nonlinear loads in electric distribution networks causes many problems due to the high level of harmonic currents. This paper proposes a new technique for controlling a single phase shunt active power filter based on a selective compensation using the newly developed technique of harmonic control arrays. Simulation results confirm the appropriate selective harmonic compensa...
متن کاملClosed-Loop Compensation of the Quadrature Error in MEMS Vibratory Gyroscopes
In this paper, a simple but effective method for compensation of the quadrature error in MEMS vibratory gyroscope is provided. The proposed method does not require any change in the sensor structure, or additional circuit in the feedback path. The mathematical relations of the proposed feedback readout system were analyzed and the proposed solution assures good rejection capabilities. Based on ...
متن کاملA New Strategy for Simultaneous Compensation of Instantaneous Reactive Power and Harmonics of Non-Linear Loads (RESEARCH NOTE)
This paper presents a new control method for simultaneous compensation of instantaneous reactive power and current harmonics by parallel active filters (PAFs). Reference compensating currents of PAF are calculated using the subtraction of instantaneous power from its average value. In this way, it is possible omitting high/low pass filter(s) from the control circuit of PAF, which usually result...
متن کاملHarmonic Elimination of 25 kV AC Electric Railways Utilizing a New Hybrid Filter Structure
Thyristor rectifiers are widely used in electric railways in order to control the speed. As a consequence of their usage in addition to substantial input lead current, an enormous amount of harmonics is injected into the grid. To avoid such harmonics as well as reactive power compensation, reactive power hybrid filters consisting of active and passive filters are utilized. Regarding different p...
متن کاملElimination of Harmonic Force and Torque in Active Magnetic Bearing Systems with Repetitive Control and Notch Filters
Harmonic force and torque, which are caused by rotor imbalance and sensor runout, are the dominant disturbances in active magnetic bearing (AMB) systems. To eliminate the harmonic force and torque, a novel control method based on repetitive control and notch filters is proposed. Firstly, the dynamics of a four radial degrees of freedom AMB system is described, and the AMB model can be described...
متن کامل