Legionella species and serogroups in Malaysian water cooling towers: identification by latex agglutination and PCR-DNA sequencing of isolates.
نویسندگان
چکیده
In this study, we investigated the distribution of Legionella species in water cooling towers located in different parts of Malaysia to obtain information that may inform public health policies for the prevention of legionellosis. A total of 20 water samples were collected from 11 cooling towers located in three different states in east, west and south Malaysia. The samples were concentrated by filtration and treated with an acid buffer before plating on to BCYE agar. Legionella viable counts in these samples ranged from 100 to 2,000 CFU ml(-1); 28 isolates from the 24 samples were examined by latex agglutination as well as 16S rRNA and rpoB PCR-DNA sequencing. These isolates were identified as Legionella pneumophila serogroup 1 (35.7%), L. pneumophila serogroup 2-14 (39%), L. pneumophila non-groupable (10.7%), L. busanensis, L. gormanii, L. anisa and L. gresilensis. L. pneumophila was clearly the predominant species at all sampling sites. Repeat sampling from the same cooling tower and testing different colonies from the same water sample showed concurrent colonization by different serogroups and different species of Legionella in some of the cooling towers.
منابع مشابه
Isolation of Legionella Pneumophila Serogroups 1, 8 & 10 (Causative Agents of Legionnaires\' Disease) from Water Sources in Tehran, Iran
In this survey, 187 samples collected from 9 different sources of water in Tehran such as: water coolers, neonates incubators, water bathes (37° C), little pools in parks or squares, cooling towers, hot or cold water taps, were examined for Legionnaires' disease agents. Inoculating water samples on selective and nonselective media resulted in isolation of several strains of gram negative bact...
متن کاملPrevalence and Molecular Characteristics of Waterborne Pathogen Legionella in Industrial Cooling Tower Environments
Cooling towers are a source of Legionnaires' disease. It is important from a public health perspective to survey industrial cooling towers for the presence of Legionella. Prospective surveillance of the extent of Legionella pollution was conducted at factories in Shijiazhuang, China between March 2011 and September 2012. Overall, 35.7% of 255 industrial cooling tower water samples showed Legion...
متن کاملLegionella species isolated from cooling towers in Kuala Lumpur.
Three building complexes in Kuala Lumpur were surveyed for the presence of legionellae in cooling towers. The organisms were grown from 12 out of 46 samples of water collected from 30 towers. L. pneumophila serogroups 1 and 7 were the commonest serogroups isolated. None belonged to the Pontiac subgroup of L. pneumophila serogroup 1.
متن کاملSerological cross-reaction between Legionella spp. and Capnocytophaga ochracea by using latex agglutination test.
Cross-reactivity between Legionella spp. and Capnocytophaga ochracea was noted by latex agglutination tests (Serobact Legionella; Disposable Products, Adelaide, Australia). Four of 11 (36%) C. ochracea isolates agglutinated with latex reagents designed to identify Legionella pneumophila serogroups. C. ochracea isolated on buffered charcoal yeast extract media may give false-positive results in ...
متن کاملComparison of conventional culture and real-time quantitative PCR using SYBR Green for detection of Legionella pneumophila in water samples
The genus Legionella comprises more than 40 species and 64 serogroups with approximately half of those species associated with human diseases. Legionella pneumophila Serogroup 1 is the most common pathogenic species and is responsible for up to 80% of legionellosis cases in the world. Legionella levels in water are assessed routinely by culture on a selective medium, but its slow growth is a se...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
عنوان ژورنال:
- Journal of water and health
دوره 8 1 شماره
صفحات -
تاریخ انتشار 2010