this paper presents a new control method for a three-phase four-wire unified power quality conditioner (upqc) to deal with the problems of power quality under distortional and unbalanced load conditions. the proposed control approach is the combination of instantaneous power theory and synchronous reference frame (srf) theory which is optimized by using a self-tuning filter (stf) and without using load or filter currents measurement. in this approach, load and source voltages are used to generate the reference voltages of series active power filter (apf) and source currents are used to generate the reference currents of shunt apf. therefore, the number of current measurements is reduced and system performance is improved. the performance of proposed control system is tested for cases of power factor correction, reducing source neutral current, load balancing and current and voltage harmonics in a three-phase four-wire system for distortional and unbalanced loads. results obtained through matlab/simulink software show the effectiveness of proposed control technique in comparison to the conventional p-q method.
منابع مشابه
Improving the performance of UPQC under unbalanced and distortional load conditions: A new control method
This paper presents a new control method for a three-phase four-wire Unified Power Quality Conditioner (UPQC) to deal with the problems of power quality under distortional and unbalanced load conditions. The proposed control approach is the combination of instantaneous power theory and Synchronous Reference Frame (SRF) theory which is optimized by using a self-tuning filter (STF) and without us...
متن کاملA New Approach Based on Instantaneous Power Theory for Improving the Performance of UPQC Under Unbalanced and Distortional Load Conditions
In order to deal with power quality problems under distortional and unbalanced load conditions, this paper presents a new control method for a four-wire three-phase unified power quality conditioner (UPQC) which is based on instantaneous power p-q theory. The proposed control approach is based on instantaneous power and is optimized by using a self-tuning filter (STF), without using any low-pas...
متن کاملA Quantities Method of Induction Motor under Unbalanced Voltage Conditions
The most complete definition for the voltage unbalance is using complex voltage unbalance factor (CVUF) that consists of its magnitude and angle. Unfortunately, the definition did not distinguish between undervoltage and overvoltage unbalance conditions. In this paper, the analysis of the motor is performed using the method of symmetrical component and MATLAB software is used to investigate the...
متن کاملHysteresis Control for Shunt Active Power Filter under Unbalanced Three-Phase Load Conditions
This paper focuses on a four-wire shunt active power filter (APF) control scheme proposed to improve the performance of the APF. This filter is used to compensate harmonic distortion in three-phase four-wire systems. Several harmonic suppression techniques have been widely proposed and applied to minimize harmonic effects. The proposed control scheme can compensate harmonics and reactive power ...
متن کاملUsing WPT as a New Method Instead of FFT for Improving the Performance of OFDM Modulation
Orthogonal frequency division multiplexing (OFDM) is used in order to provide immunity against very hostile multipath channels in many modern communication systems.. The OFDM technique divides the total available frequency bandwidth into several narrow bands. In conventional OFDM, FFT algorithm is used to provide orthogonal subcarriers. Intersymbol interference (ISI) and intercarrier interferen...
متن کاملA Control Method in dq Synchronous Frame for PWM Boost Rectifier under Generalized Unbalanced Operating Conditions
This paper proposes a new control scheme for regulating the instantaneous power for pwm boost type rectifiers under generalized unbalanced operating conditions. By nullifying the oscillating components of instantaneous power at the poles of the converter instead of the front-end through solving a set of nonlinear control equations in real time, the harmonics in the output dc voltage can be el...