VOLT-SECOND BALANCE METHOD FOR MITIGATION OF INRUSH CURRENT IN SINGLE PHASE TRANSFORMERS
نویسندگان
چکیده
منابع مشابه
Volt-second Balance Method for Mitigation of Inrush Current in Single Phase Transformers
During the transient period at the start of transformer energization, it experiences a flux linkage that is up to twice its nominal steady state value and saturates the core. This causes a large inrush current to flow which affects the power system stability and power quality especially when the source is weak. Sequential phase energization technique and addition of neutral resistor are the maj...
متن کاملMitigation Transformer Inrush Current Using Modified Transient Current Limiter
This study presents a modified transient current limiter (MTCL) for mitigation the inrush current of transformers. The MTCL is based on conventional transient current limiter (TCL), which, its configuration is modified to overcome the TCL drawbacks of operation. The proposed MTCL offers lower power losses and voltage/current THD during normal operation mode. It needs only one limiting reactor i...
متن کاملA Method for Calculation of the Inrush Current in Single Phase Transformer including the Residual Flux
A field-circuit method for simulation of transients in a single-phase, two-winding transformer has been given. The magnetic field excited by the winding currents has been analyzed, and integral parameters have been determined. Including the equivalent circuit parameters and the magnetic residual flux in the silicon steel core, the developed method has been implemented for the transitional state...
متن کاملHarmonic Modeling of Inrush Current in Core Type Power Transformers Using Hartley Transform
This paper presents a new method for evaluation and simulation of inrush current in various transformers using operational matrices and Hartley transform. Unlike most of the previous works, time and frequency domain calculations are conducted simultaneously. Mathematical equations are first represented to compute the inrush current based on reiteration and then Hartley transform is used to stud...
متن کاملMitigation of Inrush Current of Transformer using Voltage Sag Compensator
In the power system voltage sag become the important issue for industries. According to the survey 92% of the interruptions at industrial installations are voltage sag related. In various companies voltage sag may affect many manufactures and introduce sufficient losses in the power system. The voltage sag compensator, based on a transformer coupled series connected voltage source inverter, is ...