Study on Regional Suitability of Heat-Source Tower Heat Pump
نویسندگان
چکیده
To address the regional applicability of heat-source tower heat pumps (HSTHPs), a mathematical model HSTHPs was established and experimentally verified. In different thermal zones, seasonal operation characteristics were investigated in winter summer conditions. The results showed that, heating performance factor (HSPF) value cold zone is lowest, but it can reach 2.40 winter, HSPF values hot-summer warm-winter (HSWW) A, cold-winter (HSCW) mild are all greater than 2.70. energy efficiency ratio (SEER) for four zones above 4.70 summer. Except severe zone, have good prospects other particularly with high 2.77 SEER 5.43, respectively.
منابع مشابه
Research on Ground Source Heat Pump Design
One of world’s largest uses of energy is the heating and cooling of buildings. Ground Source Heat Pumps (GSHP) provide a more energy efficient way to meet building energy needs than conventional alternatives. At a relatively shallow depth, the ground temperature is nearly constant year round providing a reliable heat source or sink for the operation of a heat pump. The design of such systems is...
متن کاملHeat transfer analysis of underground U-type heat exchanger of ground source heat pump system
BACKGROUND Ground source heat pumps is a building energy conservation technique. The underground buried pipe heat exchanging system of a ground source heat pump (GSHP) is the basis for the normal operation of an entire heat pump system. METHODS Computational-fluid-dynamics (CFD) numerical simulation software, ANSYS-FLUENT17.0 have been performed the calculations under the working conditions o...
متن کاملAir Source Heat Pump for Northern Climates Part I: Simulation of Different Heat Pump Cycles
متن کامل
Performance Comparison of Hydronic Secondary Loop Heat Pump and Conventional Air-Source Heat Pump
In residential heat pump systems, the motivation for secondary loop systems is to allow for the use of flammable or toxic refrigerants with lower global warming potentials than the currently employed HFC refrigerants. The addition of radiant panels as integral building components (embedded in concrete at construction or attached to the underside of wood flooring) is becoming more common. Combin...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
ژورنال
عنوان ژورنال: Advances in transdisciplinary engineering
سال: 2022
ISSN: ['2352-751X', '2352-7528']
DOI: https://doi.org/10.3233/atde220305