A Review of Faults Detectable by Gas-in-Oil Analysis in Transformers
IEC Publication 60599 [1] provides a coded list of faults detectable by dissolved gas analysis (DGA): PD = partial discharges, D1 = discharges of low energy, D2 = discharges of high energy, T1 = thermal faults of temperature < 300 oC, T2 = thermal faults of temperature 300 oC < T < 700 oC, T3 = thermal faults of temperature > 700 oC. The IEC TC10 databases of DGA results corresponding to faults...
متن کاملInsulated Power Transformers for Improved PD Detection and Localization
A simple and commonly used way to locate PD in GIS is the measurement in time domain (time-offlight). The time difference between the arrivals of the PD impulse on two UHF sensors is used for localization. The new developed method presented here uses the frequency domain. The basic idea is the displacement law of Fourier transformation. The interference phenomena of superposed signals from two ...
متن کاملDetection in Spacer of Gas-Insulated Switchgears
With the increasing demand for precise condition monitoring and diagnosis of 11 gas-insulated switchgears (GIS), it has become a challenge to improve the detection sensitivity of 12 partial discharge (PD) induced in the GIS spacer. This paper deals with the elimination of the 13 capacitive component from the phase resolved partial discharge (PRPD) signal generated in GIS 14 spacer based on the ...
متن کاملRemote Monitoring of Incipient Faults Using Gprs in Power Transformers
− One of the most applied procedures for detention of incipient faults in power transformers, such as partial discharges, electrical arcing and overheating, is the analysis of the concentration of gases dissolved in the isolating mineral oil. This analysis usually is carried through in a laboratory through chromatography in gaseous phase. Although it presents trustworthy results the chromatogra...
متن کاملA NEURO-FUZZY TECHNIQUE FOR DISCRIMINATION BETWEEN INTERNAL FAULTS AND MAGNETIZING INRUSH CURRENTS IN TRANSFORMERS
This paper presents the application of the fuzzy-neuro method toinvestigate transformer inrush current. Recently, the frequency environment ofpower systems has been made more complicated and the magnitude of the secondharmonic in inrush current has been decreased because of the improvement of caststeel. Therefore, traditional approaches will likely mal-operate in the case ofmagnetizing inrush w...