Heat extraction capacity and its attenuation of deep borehole heat exchanger array

نویسندگان

چکیده

A model is proposed to analyze the heat transfer of deep borehole exchanger (DBHE)arrays. Based on this, a dimension reduction algorithm for numerical simulation DBHE arrays, which can improve calculation speed by several orders magnitude compared with that CFD software. An index extraction capacity (HECI) adopted evaluate arrays. The influence spacing, operation time, annual heating duration, terrestrial flow rate, depth, soil thermal parameters, pipe diameter and circulating fluid rate array its attenuation are analyzed. results show duration all have apparent while others only capacity. According results, when arrays service lifetime 20–50 years, recommended spacing range 40–70 m.

برای دانلود باید عضویت طلایی داشته باشید

برای دانلود متن کامل این مقاله و بیش از 32 میلیون مقاله دیگر ابتدا ثبت نام کنید

اگر عضو سایت هستید لطفا وارد حساب کاربری خود شوید

منابع مشابه

Quality Control of Borehole Heat Exchanger Systems

The vast growing market for borehole heat exchangers (BHE’s) requires great efforts of quality assurance in design and construction. Within a research project funded by the German Federal Ministry of Economics and Technology a consortium consisting of the University of Applied Sciences at Biberach (UASB), the University of Karlsruhe (EIFER, GI) and the Bavarian Centre of Applied Energy Research...

متن کامل

Review Heat Exchanger: Research Development of Self-rotating Inserts in Heat Exchanger Tubes

Heat exchangers are widely used in power engineering and industrial applications, many techniques such as coiled tube, surface tension devices, rough surfaces, extended surfaces have been investigated to enhancethermal performance and to minimize the cost and size of the heat exchanger equipment. One of the most important techniques is tube insert. In general,tube inserts can be classified into...

متن کامل

Sensitivity analysis on the performance of a ground source heat pump equipped with a double U-pipe borehole heat exchanger

Ground Source Heat Pumps (GSHP) are economically and environmentally advantageous for the heating and cooling of buildings, provided that the long-term sustainability of the thermal exploitation of the soil is ensured. In particular, the performance of a closed-loop Borehole Heat Exchanger (BHE) strongly depends on the geometrical and physical properties of its components and on the thermo-hydr...

متن کامل

Analysis of Geo-Temperature Restoration Performance under Intermittent Operation of Borehole Heat Exchanger Fields

Intermittent operation can improve the coefficient of performance (COP) of a ground source heat pump (GSHP) system. In this paper, an analytical solution to analyze the geo-temperature restoration performance under intermittent operation of borehole heat exchanger (BHE) fields is established. For this purpose, the moving finite line source model is combined with the g-function and the superposi...