Effect of Working Fluid-Filling Ratio Combination on Thermosyphon Performance as Add-In Enhancer for Indoor Air Conditioning Devices
نویسندگان
چکیده
An experimental study is presented to account for the implementation of a two-phase closed thermosyphon pipe, energy-saving purposes, in air conditioning systems context COVID-19. The setup consisted 0.5 m × 0.0127 type L copper pipe which was employed as body heat exchanger; an electric resistance heater 0.1 length located at bottom; and 0.25 water-cooled concentric condenser top. evaluation conducted employing acetone, ethanol, distilled water working fluids; ranging supplied evaporator from 25 125 W filling ratio 20% 40% total inner volume thermosyphon. From data obtained, it found that ethanol fluid most susceptible changes operation conditions. Contrarily, deliver consistent performance, up point that, analysed setup, considered be independent both, flow ratio. Meanwhile, acetone only tested displays directly proportional behaviour between absorption dissipation. compiling data, response surfaces were constructed used direct rough optimization tools. information provided by this approach particularly useful introduced modelling design purposes. Based on results, within ranges 34%<ϕ<40% 75 W<Q˙Evap<125 W, suitable use purposes applications.
منابع مشابه
optimum selection of liquid desiccants as working fluid for solar air conditioning systems
0
متن کاملEffect of Height Difference on The Performance of Two-phase Thermosyphon Loop Used in Air-conditioning System
Two-phase thermosyphon loops (TPTLs) are widely used in air-conditioning field for heat recovery and free cooling utilization in recent years. The height difference between the condenser and the evaporator is always considered as the driven force of thermosyphon. However, experiments show the cooling capacity of the TPTLs is not linearly improved with the increase of the height difference. So, ...
متن کاملA review of portable air cleaner devices: purification processes, performance standards, effectiveness in controlling indoor air pollutants
Background and objective: Indoor air pollutants are among the five most important environmental health risks. In recent years, concerns regarding indoor air in buildings have increased. In this review, studies conducted on portable air cleaners have been investigated. Materials and methods: After determining the keywords and conducting comprehensive searches in the internet databases, taking i...
متن کاملTHE EFFECT OF TYPE OF SPECIFIC HEATS RATIO OF WORKING FLUID ON THE THERMAL PERFORMANCE OF STANDARD OTTO CYCLE
In thermodynamic analysis of internal combustion engine, the specific heats of working fluid is considered to be constant. Due to specific heats are functions of operation temperature of cycle, this consideration cause to several errors in the thermal analysis. In this paper, standard Otto cycle with three various types of specific heats ratios has been analyzed numerically and effect of these ...