An Improved Dual Second-Order Generalized Integrator Phased-Locked Loop Strategy for an Inverter of Flexible High-Voltage Direct Current Transmission Systems under Nonideal Grid Conditions
نویسندگان
چکیده
High-voltage flexible power systems, with their intrinsic characteristics, play an increasingly important role in electronic systems. Synchronization between the inverter and grid needs to be achieved by a phase-locked loop (PLL), performance of which determines quality transmission. This paper proposes PLL adapted extremely harsh conditions. Firstly, traditional synchronous reference frame dual second-order generalized integrator (DSOGI-PLL) are analyzed, errors phase-locking shortcomings these two methods presence DC components pointed out. Secondly, based on harmonic voltage, repetitive control internal model is introduced DSOGI realize real-time tracking regulation signals order suppress voltage disturbance. In addition, bias elimination frequency adaptive method proposed solve problems fluctuation achieve phase. Finally, superiority strategy verified through simulations experiments.
منابع مشابه
development and implementation of an optimized control strategy for induction machine in an electric vehicle
in the area of automotive engineering there is a tendency to more electrification of power train. in this work control of an induction machine for the application of electric vehicle is investigated. through the changing operating point of the machine, adapting the rotor magnetization current seems to be useful to increase the machines efficiency. in the literature there are many approaches wh...
15 صفحه اولAn improved synchronous reference frame current control strategy for a photovoltaic grid-connected inverter under unbalanced and nonlinear load conditions
In recent years, renewable energy sources have been considered the most encouraging resources for grid and off-grid power generation. This paper presents an improved current control strategy for a three-phase photovoltaic grid-connected inverter (GCI) under unbalanced and nonlinear load conditions. It is challenging to suppress the harmonic content in the output current below a pre-set value in...
متن کاملAn LCL-filtered Single-phase Multilevel Inverter for Grid Integration of PV Systems
Integration of the PV into the electrical grid needs power electronic interface. This power electronic interface should have some key features and should come up with grid codes. One of the important criteria is the quality and harmonic contents of the current being injected to the grid. High-order harmonics of the grid current should be very limited (lower than 0.3% of the fundamental current)...
متن کاملLow Voltage Ride Through Enhancement Based on Improved Direct Power Control of DFIG under Unbalanced and Harmonically Distorted Grid Voltage
In the conventional structure of the wind turbines along with the doubly-fed induction generator (DFIG), the stator is directly connected to the power grid. Therefore, voltage changes in the grid result in severe transient conditions in the stator and rotor. In cases where the changes are severe, the generator will be disconnected from the grid and consequently the grid stability will be attenu...
متن کاملDistributed Voltage and Current Control of Multi-terminal High-voltage Direct Current Transmission Systems
High-voltage direct current (HVDC) is a commonly used technology for long-distance power transmission, due to its low resistive losses and low costs. In this paper, a novel distributed controller for multi-terminal HVDC (MTDC) systems is proposed. Under certain conditions on the controller gains, it is shown to stabilize the MTDC system. The controller is shown to always keep the voltages close...
متن کاملذخیره در منابع من
با ذخیره ی این منبع در منابع من، دسترسی به آن را برای استفاده های بعدی آسان تر کنید
ژورنال
عنوان ژورنال: Processes
سال: 2023
ISSN: ['2227-9717']
DOI: https://doi.org/10.3390/pr11092634